2 cs3 control signals, Table 8-1. cs3 control signals – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instruction Manual User Manual
Page 205
8.2 CS3 CONTROL SIGNALS
Loading CS3 connects the 53MC5000 Controller function blocks for operation as a Ratio (PID) Con-
troller. As shown in Figure 8-1, CS3 provides nine control signals which are described in Table 8-1:
Table 8-1. CS3 Control Signals
Control
Signal
Definition
Cord
Set
ITB
Rear
Term
Board
Signal
AI0 -
Controlled
Variable
This analog input signal represents the value of
the process variable from the controlled line that
must be maintained in proportion to the wild
variable.
TB1-1 (+)
TB1-2 (-)
TB1-3
1 (+)
2 (-)
3
+24 V
AI0
SC
AI1 - Wild
Variable
This analog input signal represents the value of
the process variable from the wild line.
TB1-5 (+)
TB1-6 (-)
TB1-7
4 (+)
5 (-)
6
+24 V
AI1
SC
AI2 - Additive
Feed Forward
Input
This analog input signal value is added to the
PID result to make up the Control Output value
when Auto operation is active.
TB1-9
TB1-10 (+)
TB1-11 (-)
1
7 (+)
8 (-)
+24 V
AI2
SC
AI3 - Tracking
Input
This analog input signal value becomes the
Control Output value when the Force Output
Tracking contact input is open and datapoint
L119 (Enable Output Tracking) is configured to
a 1.
TB1-13
TB1-14 (+)
TB1-15 (-)
4
9 (+)
8 (-)
+24 V
AI3
SC
AO0 - Control
Output
This is the 4-20 mA output signal that drives the
final control element.
TB1-17 (+)
TB1-18 (-)
10 (+)
11 (-)
AO0
PC
AO1
Not used.
DI0 - Force
Output
Tracking
When an open contact is present on this input,
the Control Output valve is forced to match the
Tracking Input value when datapoint L119
(Enable Output Tracking) is configured to a 1.
TB2-1 (+)
TB2-2 (-)
13 (+)
14 (-)
DI0
PC
DI1 - Ratio
Enable
When a closed contact is present on this input,
the operator can select Ratio operation with the
R/L faceplate push button.
TB2-3 (+)
TB2-4 (-)
15 (+)
14 (-)
DI1
PC
DO0 - Process
Alarm 1
This contact is closed when the Process
Variable value is not within the C103 value
setting (Alarm Limit 1 datapoint); otherwise, the
contact is open.
TB2-5 (+)
TB2-6 (-)
16 (+)
17 (-)
DO0
PC
DO1 - Process
Alarm 2
This contact is closed when the Process
Variable value is not within the C104 value
setting (Alarm Limit 2 datapoint); otherwise, the
contact is open.
TB2-7 (+)
TB2-8 (-)
18 (+)
17 (-)
DO1
PC
53MC5000 Process Control Station