8.2 CS3 CONTROL SIGNALS

Loading CS3 connects the 53MC5000 Controller function blocks for operation as a Ratio (PID) Con-
troller. As shown in Figure 8-1, CS3 provides nine control signals which are described in Table 8-1:

Table 8-1. CS3 Control Signals

Control

Signal

Definition

Cord

Set
ITB

Rear

Term

Board

Signal

AI0 -
Controlled
Variable

This analog input signal represents the value of
the process variable from the controlled line that
must be maintained in proportion to the wild
variable.

TB1-1 (+)
TB1-2 (-)
TB1-3

1 (+)
2 (-)
3

+24 V
AI0
SC

AI1 - Wild
Variable

This analog input signal represents the value of
the process variable from the wild line.

TB1-5 (+)
TB1-6 (-)
TB1-7

4 (+)
5 (-)
6

+24 V
AI1
SC

AI2 - Additive
Feed Forward
Input

This analog input signal value is added to the
PID result to make up the Control Output value
when Auto operation is active.

TB1-9
TB1-10 (+)
TB1-11 (-)

1
7 (+)
8 (-)

+24 V
AI2
SC

AI3 - Tracking
Input

This analog input signal value becomes the
Control Output value when the Force Output
Tracking contact input is open and datapoint
L119 (Enable Output Tracking) is configured to
a 1.

TB1-13
TB1-14 (+)
TB1-15 (-)

4
9 (+)
8 (-)

+24 V
AI3
SC

AO0 - Control
Output

This is the 4-20 mA output signal that drives the
final control element.

TB1-17 (+)
TB1-18 (-)

10 (+)
11 (-)

AO0
PC

AO1

Not used.

DI0 - Force
Output
Tracking

When an open contact is present on this input,
the Control Output valve is forced to match the
Tracking Input value when datapoint L119
(Enable Output Tracking) is configured to a 1.

TB2-1 (+)
TB2-2 (-)

13 (+)
14 (-)

DI0
PC

DI1 - Ratio
Enable

When a closed contact is present on this input,
the operator can select Ratio operation with the
R/L faceplate push button.

TB2-3 (+)
TB2-4 (-)

15 (+)
14 (-)

DI1
PC

DO0 - Process
Alarm 1

This contact is closed when the Process
Variable value is not within the C103 value
setting (Alarm Limit 1 datapoint); otherwise, the
contact is open.

TB2-5 (+)
TB2-6 (-)

16 (+)
17 (-)

DO0
PC

DO1 - Process
Alarm 2

This contact is closed when the Process
Variable value is not within the C104 value
setting (Alarm Limit 2 datapoint); otherwise, the
contact is open.

TB2-7 (+)
TB2-8 (-)

18 (+)
17 (-)

DO1
PC

53MC5000 Process Control Station

8-2