Table 5-9. controller modules (con0-3) – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instruction Manual User Manual
Page 162

Table 5-9. Controller Modules (CON0-3)
Title
Definition
Atom
CON0
CON1
CON2
CON3
Default
Auto Status
When Output Track Status (OVTS) is
0, 1
indicates Control Output (CO) is selected as
the output.
0 indicates the output comes from
the output push buttons.
AUT
(0-3)
L107
L131
L155
L179
0
Remote Status
When the Setpoint Track Status (SPTS) is
0, 1
indicates the setpoint is derived from the
Remote Setpoint (RSP).
0 indicates it comes
from the setpoint push buttons.
RMT
(0-3)
L108
L132
L156
L180
0
Reverse Valve
This parameter specifies the location of
Open/Close indicators in the control display.
1 means that 20 mA closes the valve. 0
indicates that 20 mA opens the valve.
RSV
(0-3)
L109
L133
L157
L181
0
Alarm A Active
See Control Alarm Mode (AIX).
PA1
(0-3)
L110
L134
L158
L182
0
Alarm B Active
See Control Alarm Mode (AIX).
PA2
(0-3)
L111
L135
L159
L183
0
Auto Switch
This parameter is used in conjunction with
Auto Enable (AE) to allow the Control Output
(OUT) to become the auto/manual generator
result Output (OUT).
SWA
(0-3)
L112
L136
L160
L184
0
Remote Switch
This parameter is used in conjunction with
Remote Setpoint Enable (RE) to allow the
modified Remote Setpoint to become the
setpoint value to the setpoint generator.
SWR
(0-3)
L113
L137
L161
L185
0
Auto Enable
When this parameter is set to a
1, the Control
Output (CO) becomes the auto/manual
generator result Output (OUT) if the Auto
Switch (SWA) is set to a
1 by the A/M push
button or user program (F-TRAN, FCIM, or
FCS wire list).
AE
(0-3)
L114
L138
L162
L186
1