Table 13-3. CS22 Two Loop Override Controller Datapoints

Data-

point

Table

Module

Title and Function

Default

CON1 Control Related Datapoints

C116

5-9

CON0

Controller Lower Range - Enter a value that represents in
engineering units the Primary Control Lower Range value.

0

C142

5-9

CON1

Proportional Band - Is the percent of error required to move
the output full scale for proportional action.

100

C143

5-9

CON1

Reset Time - Is the number of minutes per repeat of integral
action. It is mutually exclusive with Manual Reset.

0

C144

5-9

CON1

Rate Time - Represents the minutes proportional action is
advanced.

0

C147

5-9

CON1

Manual Reset - It determines the output valve position when
the controller is in Auto and the error = 0. It is mutually
exclusive with Reset Time.

50

L130

5-9

CON1

Reverse Switch - 0 = Control Output Limiting

if Limiting

Variable

; 1 = Control Output Limiting

if Limiting

Variable

.

1

L138

5-9

CON1

Auto Enable - Controller output is from a PID algorithm when
set to 1 and A/M push button is in Auto.

1

C151

5-9

CON1

Controller Span - Enter a value, that when added to the
Limiting Controller Lower Range value, will produce the
control upper range value in engineering units.

100

C152

5-9

CON1

Controller Lower Range - Enter a value that represents in
engineering units the Limiting Control Lower Range value.

0

AO1 - Override Status

L473

5-5

AO1

0-20 mA Output - 0 = 4-20 mA signal; 1 = 0-20 mA signal.
If left at the default value of 0, then 4 mA = Primary Variable
Loop controls AO0 output and 20 mA = Limiting Variable
Loop controls AO0 output.
If configured to a 1, then 0 mA = Primary Variable Loop
controls AO0 output and 20 mA = Limiting Variable Loop
controls AO0 output.

0

DI0 - Remote Enable Primary

L264

5-6

DI0

Contact Input Invert - Normally, the Primary Variable Loop
Remote Enable is permitted if DI0 is closed (datapoint L115 -
Remote Setpoint Enable is set to 1 by DI0). Set to 1 to
reverse the DI0 condition required to permit the Primary
Variable Loop Remote Enable (DI0 open = Primary Variable
Loop Remote Enable).

0

DI1 - Remote Enable Limiting

L265

5-6

DI1

Contact Input Invert - Normally, the Limiting Variable Loop
Remote Enable is permitted if DI1 is closed (datapoint L139 -
Remote Setpoint Enable is set to 1 by DI1). Set to 1 to
reverse the DI1 condition required to permit the Limiting
Variable Loop Remote Enable (DI1 open = Limiting Variable
Loop Remote Enable).

0

4 of 5

Section 13. CS22 - Two Loop Override Controller

13-9