Table 6-3. CS1 Single Loop CON0 Datapoints
Data-
point
Table
Module
Title and Function
De-
fault
AO0 - Control Out (Cont)
L122
5-9
CON0
Hard Manual Limit - 1 = apply output limits to the final output
of the Auto-Manual Generator. It affects both the manual
push buttons and the controller’s result. 0 = do not apply
limits.
1
C109
5-9
CON0
Output High Limit - Sets maximum Control Output signal
value in engineering units.
100
C110
5-9
CON0
Output Low Limit - Sets minimum Control Output signal value
in engineering units.
0
C118
5-9
CON0
Output Slew Rate - It is a rate limit applied to the output
value. When configured to a non-zero value, the output from
the Auto-Selector is only allowed to change by this amount
each scan time. A zero disables output slewing. It does not
affect manual operation.
0
CON0 Control Related Datapoints
C106
5-9
CON0
Proportional Band - Is the percent of error required to move
the output full scale for proportional action.
100
C107
5-9
CON0
Reset Time - Is the number of minutes per repeat of integral
action. It is mutually exclusive with Manual Reset.
0
C108
5-9
CON0
Rate Time - Represents the minutes proportional action is
advanced.
0
C111
5-9
CON0
Manual Reset - It determines output valve position when the
controller is in Auto and the error = 0. It is mutually
exclusive with Reset Time.
50
L106
5-9
CON0
Reverse Switch - 0 = Control Output
↑
if PV
↑
; 1 = Control
Output
↓
if PV
↑
.
1
L114
5-9
CON0
Auto Enable - Controller output is from the PID algorithm
when set to 1 and A/M push button is in Auto.
1
C115
5-9
CON0
Controller Span - Enter a value, that when added to the
Controller Lower Range value, will produce the control upper
range value in engineering units.
100
C116
5-9
CON0
Controller Lower Range - Enter a value that represents in
engineering units the control lower range value.
0
AO1 - Retransmitted PV
L473
5-5
AO1
0-20 mA Output - 0 = 4-20 mA signal; 1 = 0-20 mA signal.
Enter a value that matches the required Process Variable
input signal range of the chained controller or device.
0
DI0 - Force Output Tracking
L264
5-6
DI0
Contact Input Invert - Normally, Force Output Tracking is
enabled if DI0 is open (and datapoint L119 - Enable Output
Tracking = 1). Set to 1 to reverse the DI0 condition required
to activated output tracking (DI0 closed = Force Output
Tracking).
0