5 analog output modules (ao0-3), Table 5-5. analog output modules (ao0-3) – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instruction Manual User Manual

Page 153

background image

5.5 ANALOG OUTPUT MODULES (AO0-3)

The Analog Output Modules (AO0-3) are used to configure the characteristics of each output. Outputs AO2 and AO3 are active only if
the appropriate hardware option is installed. The four Analog Output Modules are provided in Table 5-5. Each one can be configured
separately.

Table 5-5. Analog Output Modules (AO0-3)

Title

Definition

Atom

AO0

AO1

AO2

AO3

Default

Analog Output

The value in this datapoint represents
the percent of output to be generated by
hardware (e.g., 100% output = 20 mA).

AO

(0-3)

C000

C001

C002

C003

0

Signal Base

This value specifies the signaling range
of the output:
0 - 4-20 mA
1 - 0-20 mA

BASE

(0-3)

L472

L473

L474

L475

0

Calibrate Zero

This is the calibration zero adjustment.
This parameter

is factory set and

should not need adjustment under
normal operation. See Section 18.4 for
additional information.

COZ

(0-3)

B267

B268

Calibrate Span

This is the calibration span adjustment.
This parameter

is factory set and

should not need adjustment under
normal operation. See Section 18.4 for
additional information.

COS
(0-3)

C300

C301

Tag Name

It is an assignable 10 character name for
the analog output (AO0).

TAG

A244

A245

A246

A247