5.5 ANALOG OUTPUT MODULES (AO0-3)
The Analog Output Modules (AO0-3) are used to configure the characteristics of each output. Outputs AO2 and AO3 are active only if
the appropriate hardware option is installed. The four Analog Output Modules are provided in Table 5-5. Each one can be configured
separately.
Table 5-5. Analog Output Modules (AO0-3)
Title
Definition
Atom
AO0
AO1
AO2
AO3
Default
Analog Output
The value in this datapoint represents
the percent of output to be generated by
hardware (e.g., 100% output = 20 mA).
AO
(0-3)
C000
C001
C002
C003
0
Signal Base
This value specifies the signaling range
of the output:
0 - 4-20 mA
1 - 0-20 mA
BASE
(0-3)
L472
L473
L474
L475
0
Calibrate Zero
This is the calibration zero adjustment.
This parameter
is factory set and
should not need adjustment under
normal operation. See Section 18.4 for
additional information.
COZ
(0-3)
B267
B268
Calibrate Span
This is the calibration span adjustment.
This parameter
is factory set and
should not need adjustment under
normal operation. See Section 18.4 for
additional information.
COS
(0-3)
C300
C301
Tag Name
It is an assignable 10 character name for
the analog output (AO0).
TAG
A244
A245