Table 15-3. CS41 Four Loop Controller Datapoints

Data-

point

Table

Module

Title and Function

De-

fault

CON2 Control Loop 3 Related Datapoints (Cont)

C183

5-9

CON2

Manual Reset - It determines Loop 3 output valve position
when the controller is in Auto and the error = 0. It is mutually
exclusive with Reset Time.

50

L154

5-9

CON2

Reverse Switch - 0 = Loop 3 Control Output

if Loop 3 PV

; 1 = Loop 3 Control Output

if Loop 3 PV

.

1

L162

5-9

CON2

Auto Enable - Controller output is from the Loop 3 PID
algorithm when set to 1 and A/M push button is in Auto.

1

C187

5-9

CON2

Controller Span - Enter a value, that when added to the Loop
3 Controller Lower Range value, will produce the Loop 3
control upper range value in engineering units.

100

C188

5-9

CON2

Controller Lower Range - Enter a value that represents in
engineering units the Loop 3 control lower range value.

0

AO3 - Control Output Loop 4

L475

5-5

AO3

0-20 mA Output - 0 = 4-20 mA signal; 1 = 0-20 mA signal.
Enter a value to match the Loop 4 output valve requirements.

0

L192

5-9

CON3

Manual Fallback Disable - 0 = always power up in manual for
Loop 4; 1 = auto/manual selector unchanged at power up.

0

L194

5-9

CON3

Hard Manual Limit - 1 = apply output limits to the final output
of the Loop 4 Auto-Manual Generator. Affects both the
manual push buttons and the controller’s result. 0 = do not
apply limits.

1

C217

5-9

CON3

Output High Limit - Sets maximum Loop 4 Control Output
signal value in engineering units.

100

C218

5-9

CON3

Output Low Limit - Sets minimum Loop 4 Control Output
signal value in engineering units.

0

C226

5-9

CON3

Output Slew Rate - It is a rate limit applied to the output
value. When configured to a non-zero value, the output from
the Loop 4 Auto-Selector is only allowed to change by this
amount each scan time. A zero disables output slewing. It
does not affect manual operation.

0

CON3 Control Loop 4 Related Datapoints

C214

5-9

CON3

Proportional Band - Is the Loop 4 percent of error required to
move the output full scale for proportional action.

100

C215

5-9

CON3

Reset Time - Is the number of minutes per repeat of integral
action for Loop 4. It is mutually exclusive with Manual Reset.

0

C216

5-9

CON3

Rate Time - Represents the minutes Loop 4 proportional
action is advanced.

0

C219

5-9

CON3

Manual Reset - It determines the Loop 4 output valve
position when the controller is in Auto and the error = 0. It is
mutually exclusive with Reset Time.

50

L178

5-9

CON3

Reverse Switch - 0 = loop 4 Control Output

if Loop 4 PV

;

1 = Loop 4 Control Output

if Loop 4 PV

.

1

L186

5-9

CON3

Auto Enable - Controller output is from the Loop 4 PID
algorithm when set to 1 and A/M push button is in Auto.

1

8 of 13

53MC5000 Process Control Station