Table 5-4. Analog Input Modules (AI0-8)

Title

Definition

Atom

AI0

AI1

AI2

AI3

AI4

AI5

AI6

AI7

AI8

Default

Square Root
Signal

This value specifies the
characteristics of the signaling input
as either linear or square root.
0 - Linear
1 - Square Root
When square root is selected, input
signals less than 1% after
linearization (10% input range)
force the input to its zero value.

SQRT

(0-8)

L440

L441

L442

L443

L444

L445

L446

L447 L448

0

Calibrate
Zero

This is the calibration zero
adjustment. This parameter

is

factory set and should not need
adjustment
under normal
operation. See Section 18.4 for
additional information.

CIZ

(0-8)

B263

B264 B265

B266

Calibrate
Span

This is the calibration span
adjustment. This parameter

is

factory set and should not need
adjustment
under normal
operation. See Section 18.4 for
additional information.

CIS

(0-8)

C296

C297 C298

C299

Frequency
Input

This specifies whether the signaling
input is a voltage or frequency.
0 - Voltage
1 - Frequency
The value of the input becomes
(Span X Freq) + Zero
See Section 1, Specifications, for
duty cycle input requirements.

FREQ

(0-8)

L468

L469

L470

L471

0