Table 5-14. System Module

Title

Definition

Atom

Data-

point

De-

fault

Number of
Groups

This parameter dictates the number of groups that the display list represents. In the pop-up
locator grid, this parameter represents the number of columns in the matrix. Valid numbers are
from 1 to 8. When B017 contains a 1, F1 is the page forward push button and F2 is the page
backward push button. When B017 contains a number greater than 1, F1 is the next group push
button and F2 is the next display push button.
An example would be a two loop controller (CON0 and CON1) where it is desirable to have
three display groups (three display grid columns): datapoint B017 would be configured to 3.

MDG

B017

1

Number of
Displays
Per Group

This parameter is the number of displays contained within each group. Each group must have
the same number of displays. In the pop-up locator grid, this parameter represents the number
of rows in the matrix. Valid numbers are from 1 to 8.
An example would be a two loop controller (CON0 and CON1) where it is desirable to have
three display groups, each containing three displays (three display grid columns and three
display grid rows): datapoint B017 above = 3 and datapoint B018 would also be configured to 3.

MDS

B018

5

Loop Select

Control Module Selector (CON-0 = 0, CON-1 = 1, CON-2 = 2, CON-3 = 3)

LPS

B385

0

Control
Mode

PID Control Mode
1 - P, 2 - PI, 3 - PID, 4 - PD
If the ratio of Process Dead Time (Wp) and Process Time Constant (Tp) is greater than 0.5, then
this datapoint should be set to 3 for PID Control Mode.

CM

B386

0

Limit Settling
Time

This parameter corresponds to the time, in seconds, allowed for the process to settle and for the
preliminary step-response to be detected.

TLIM

C387

0

PV
Excursion
Limit

Maximum Allowable Excursion of PV in EASY-TUNE (%)
Setting C380 will prevent excessive change in PV.

DPV

C380

0

Output Step

Step Size Change in Controller Output (

±

%)

Set large enough to cause significant but allowable PV changes. (See C378 above.)

DOUT

C381

0

Preliminary
PV Step
Disturbance

Excursion Limit for Preliminary Step Disturbance (%)
The step size chosen for C381 will cause a PV change which depends on the process gain as
well as C381 itself. C378 should be set to approximately 1/4 of that expected change. (See
C381 below.)

DPPV

C378

2