17.6 ABORTING THE EASY-TUNE SEQUENCE

If the EASY-TUNE sequence is active and the controller output is deliberately changed, the se-
quence will be aborted. The original controller output and Manual or Auto mode will be restored.
Datapoint B387, EASY-TUNE Status, will be set to

54.

If the EASY-TUNE sequence is active and datapoint L521, EASY-TUNE Abort Switch, is set to

1,

the sequence is immediately aborted. The original controller output and Manual or Auto mode will
be restored. Datapoint B387, EASY-TUNE Status, will be set to

60.

17.7 EASY-TUNE SEQUENCE COMPLETION

Upon successful completion of the EASY-TUNE sequence, the controller is returned to its original
status, with or without the new tuning parameters, depending on its initial settings. If the EASY-
TUNE algorithm encounters an abnormal event, the controller is returned to its original settings
and an error status is displayed in datapoint B387.

Section 17. EASY-TUNE