Table 6-3. cs1 single loop con0 datapoints – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instruction Manual User Manual
Page 193

Table 6-3. CS1 Single Loop CON0 Datapoints
Data-
point
Table
Module
Title and Function
De-
fault
DI1 - Remote Setpoint Enable
L265
5-6
DI1
Contact Input Invert - Normally, Remote Setpoint Enable is
permitted if DI1 is closed (datapoint L115 - Remote Setpoint
Enable is set to 1 by DI1). Set to 1 to reverse the DI1
condition required to activate remote setpoint (DI1 open =
Remote Setpoint Enable).
0
DO0 - Process Alarm 1
L288
5-7
DO0
Contact Output Invert - Normally, Process Alarm 1 is enabled
if DO0 is closed. Set to 1 to reverse the DO0 condition
required to activate Process Alarm 1 (DO0 open = the PV
value is not within the C103 limit).
0
DO1 - Process Alarm 2
L289
5-7
DO1
Output Invert - Normally, Process Alarm 2 is enabled if DO1
is closed. Set to 1 to reverse the DO1 condition required to
activate Process Alarm 2 (DO1 open = the PV value is not
within the C104 limit).
0
Alarms Related Datapoints
B335
5-9
CON0
Control Alarm Mode - Used to select one of six alarm types
or none. See Table 5-9 for details and examples.
1
C103
5-9
CON0
Alarm Limit 1 - Point in engineering units where an alarm is
triggered because the PV is not within the limit value set in
C103.
100
C104
5-9
CON0
Alarm Limit 2 - Point in engineering units where an alarm is
triggered because the PV is not within the limit value set in
C104.
0
C105
5-9
CON0
Alarm Dead Band - Sets the activation/deactivation gaps for
the alarm limit points. It is in engineering units.
2
Setpoint Related Datapoints
C114
5-9
CON0
Control Zone - A gap on both sides of setpoint. When PV is
within this gap, the proportional and integral output changes
are suppressed. Derivative output is unaffected.
0
C125
5-9
CON0
Setpoint High Limit - It is the maximum control setpoint value
allowed.
100
C126
5-9
CON0
Setpoint Low Limit - It is the minimum control setpoint value
allowed.
0
C117
5-9
CON0
Setpoint Slew Rate - It is a rate limit applied to the setpoint.
When configured to a non-zero value, the setpoint used in
the PID algorithm is only allowed to change by this amount
each scan time. The final value of the setpoint always
appears on the units display. A zero disables setpoint
slewing.
0
L118
5-9
CON0
SP Track Enable - 1 = allow setpoint to track the process
variable when in manual.
0
4 of 5
53MC5000 Process Control Station
6-8