Table 15-3. CS41 Four Loop Controller Datapoints

Data-

point

Table

Module

Title and Function

De-

fault

AI3 - Remote Setpoint Loop 2 (Is affected by Setpoint Related Datapoints) (Cont)

C279

5-4

AI3

Engineering Zero - Enter a value that represents in
engineering units the Loop 2 Remote Setpoint lower range
signal value.

0

B272

5-4

AI3

Digital Filter Index - This is a first order filter that can be
applied to the Loop 2 Remote Setpoint signal. See Table 5-4
for input values.

3

L419

5-4

AI3

0-5 V Input - Enter a value that matches the signal voltage
range of the Loop 2 Remote Setpoint signal. 1 = 0 - 5 V
input range; 0 = 1 - 5 V input range.

0

L443

5-4

AI3

Square Root Signal - It is used if the Loop 2 Remote Setpoint
input is a squared signal value that must be linearized. 0 =
input is already linear; 1 = square root to restore linearization.

0

AI4 - Process Variable Loop 3

C260

5-4

AI4

Engineering Span - Set to 100 by CS41; however, it can be
changed. Enter a value, that when added to the Engineering
Zero value, will produce an upper range value in engineering
units that represents the Loop 3 PV transducer upper range
signal value.

100

(CS41)

C280

5-4

AI4

Engineering Zero - Enter a value that represents in
engineering units the Loop 3 PV transducer lower range
signal value.

0

B273

5-4

AI4

Digital Filter Index - This is a first order filter that can be
applied to the Loop 3 PV transducer signal. See Table 5-4
for input values.

3

L420

5-4

AI4

0-5 V Input - Enter a value that matches the signal voltage
range of the Loop 3 PV transducer. 1 = 0 - 5 V range; 0 = 1 -
5 V range.

0

L444

5-4

AI4

Square Root Signal - It is used if the Loop 3 PV transducer is
a nonlinear differential pressure (DP) cell that provides a
squared signal value. 0 = input is already linear; 1 = square
root to restore linearization.

0

AI5 - Process Variable Loop 4

C261

5-4

AI5

Engineering Span - Set to 100 by CS41; however, it can be
changed. Enter a value, that when added to the Engineering
Zero value, will produce an upper range value in engineering
units that represents the Loop 4 PV transducer upper range
signal value.

100

(CS41)

C281

5-4

AI5

Engineering Zero - Enter a value that represents in
engineering units the Loop 4 PV transducer lower range
signal value.

0

B274

5-4

AI5

Digital Filter Index - This is a first order filter that can be
applied to the Loop 4 PV transducer signal. See Table 5-4
for input values.

3