Table 12-3. CS21 Two Loop Cascade Controller Datapoints

Data-

point

Table

Module

Title and Function

De-

fault

AI0 - Process Variable Primary

C256

5-4

AI0

Engineering Span - Enter a value, that when added to the
Engineering Zero value, will produce an upper range value in
engineering units that represents the PV Primary transducer
upper range signal value.

100

C276

5-4

AI0

Engineering Zero - Enter a value that represents in engi-
neering units the PV Primary transducer lower range signal
value.

0

B269

5-4

AI0

Digital Filter Index - This is a first order filter that can be
applied to the PV Primary transducer signal. See Table 5-4
for input values.

3

L416

5-4

AI0

0-5 V Input - Enter a value that matches the signal voltage
range of the PV Primary transducer. 1 = 0 - 5 V range; 0 = 1
- 5 V range.

0

L440

5-4

AI0

Square Root Signal - It is used if the PV Primary transducer
is a nonlinear differential pressure (DP) cell that provides a
squared signal value. 0 = input is already linear; 1 = square
root to restore linearization.

0

AI1 - Remote Setpoint Primary (Is affected by Setpoint Related Datapoints)

L115

5-9

CON0

Remote Setpoint Enable - This datapoint is controlled by DI1.
When DI1 is a closed contact, this datapoint is set to 1 to
allow the modified Primary Remote Setpoint to become the
value used as the control setpoint if the R/L push button is in
Remote.

0

C112

5-9

CON0

Remote Setpoint Bias (B1) - This datapoint and Remote
Setpoint Ratio (K1) allow the Remote Setpoint input to be
modified by the Setpoint Generator.
Setpoint = [Remote Setpoint X Ratio] + Bias
SP = [RSP X K1] + B1

The B1 and K1 datapoints are modified when the input signal
must be scaled to match the setpoint range desired.

0

C113

5-9

CON0

Remote Setpoint Ratio (K1) - See Remote Setpoint bias (B1)
above.

1

C257

5-4

AI1

Engineering Span - Enter a value, that when added to
Engineering Zero, will produce an upper range value in
engineering units that represents the Primary Remote
Setpoint upper range signal value.

0

C277

5-4

AI1

Engineering Zero - Enter a value that represents in
engineering units the Primary Remote Setpoint lower range
signal value.

0

B270

5-4

AI1

Digital Filter Index - This is a first order filter that can be
applied to the Primary Remote Setpoint signal. See Table
5-4 for input values.

3

L417

5-4

AI1

0-5 V Input - Enter a value that matches the signal voltage
range of the Primary Remote Setpoint. 1 = 0 - 5 V range; 0 =
1 - 5 V range.

0

1 of 6

53MC5000 Process Control Station