Table 14-3. CS40 Dual Two Loop Cascade Controller Datapoints

Data-

point

Table

Module

Title and Function

De-

fault

CON0

OUT (Setpoint from Loop 1 to Loop 3) (Cont)

C106

5-9

CON0

Proportional Band - Is the percent of error required to move
the CON0

OUT full scale for proportional action.

100

C107

5-9

CON0

Reset Time - Is the number of minutes per repeat of integral
action. It is mutually exclusive with Manual Reset.

0

C108

5-9

CON0

Rate Time - Represents the minutes proportional action is
advanced.

0

C111

5-9

CON0

Manual Reset - It determines output valve position when the
controller Loop 1 is in Auto and the error = 0. It is mutually
exclusive with Reset Time.

50

C115

5-9

CON0

Controller Span - Enter a value, that when added to the
Loop 1 Control Lower Range value, will produce the Control
upper range value in engineering units.

100

C116

5-9

CON0

Controller Lower Range - Enter a value that represents in
engineering units the Loop 1 Control lower range value.

0

C118

5-9

CON0

Output Slew Rate - It is a rate limit applied to the output
value (setpoint from Loop 1 to Loop 3). When configured to
a non-zero value, the output from the Loop 1 Auto-Selector is
only allowed to change by this amount each scan time. A
zero disables output slewing. It does not affect manual
operation.

0

AO0 - #1 Secondary Control Output (Loop 3)

L472

5-5

AO0

0-20 mA Output - 0 = 4-20 mA signal; 1 = 0-20 mA signal.
Enter a value to match the Loop 3 output valve requirements.

0

L168

5-9

CON2

Manual Fallback Disable - 0 = always power up Loop 3 in
manual; 1 = auto/manual selector unchanged at power up.

0

L170

5-9

CON2

Hard Manual Limit - 1 = apply output limits to the final output
of the Loop 3 Auto-Manual Generator. Affects both the
manual push buttons and the controller’s result. 0 = do not
apply limits.

1

C181

5-9

CON2

Output High Limit - Sets maximum Loop 3 output signal
value in engineering units.

100

C182

5-9

CON2

Output Low Limit - Sets minimum Loop 3 output signal value
in engineering units.

0

C190

5-9

CON2

Output Slew Rate - It is a rate limit applied to the output
value. When configured to a non-zero value, the output from
the Loop 3 Auto-Selector is only allowed to change by this
amount each scan time. A zero disables output slewing. It
does not affect manual operation.

0

CON 2 #1 Secondary Control Output (LOOP 3) Related Datapoints

C178

5-9

CON2

Proportional Band - Is the percent of error required to move
the Loop 3 output full scale for proportional action.

100

C179

5-9

CON2

Reset Time - Is the number of minutes per repeat of integral
action. It is mutually exclusive with Manual Reset.

0

C180

5-9

CON2

Rate Time - Represents the minutes proportional action is
advanced.

0

3 of 7

Section 14. CS40 - Dual Two Loop Cascade Controller