B.1.4 COMMUNICATION TRANSACTION EXAMPLES

Transaction A Example

- Host or SUPERVISOR-PC requests 9 bytes of data beginning at hexa-

decimal memory address 1000

H

from the controller at Datalink address 03.

1.

Host or SUPERVISOR-PC sends

INTERROGATE message.

01111110 11100011 00001001 00000000 00010000 11111100

SOH Command NUM LO ADD HI ADD LRC
+ I.A.

2.

Controller sends

RESPONSE message.

01111110 00100011 00001001 00000000 00010000 XXXXX XXXXX XXXXX LRC

SOH Command NUM LO ADD HI ADD Data 1..................Data 9
+ I.A.

Transaction B Example - Host or SUPERVISOR-PC sends two bytes of new data, to be loaded
into the controller at Datalink address 03 beginning at hexadecimal memory address 1000

H

.

1.

Host sends

CHANGE message.

01111110 10100011 00000010 00000000 00010000 00001000 00001100 11001001

SOH Command NUM LO ADD HI ADD Data 1 Data 2 LRC
+ I.A.

2.

Controller sends

RESPONSE message.

01111110 00100011 00000010 00000000 00010000 00001000 00001100 01001001

SOH Command NUM LO ADD HI ADD Data 1 Data 2 LRC
+ I.A.

3.

Host sends

ACKNOWLEDGE message.

01111110 10000011

SOH Command
+ I.A.

4.

Controller performs the change requested at end of the current program scan.

Appendix B. Communications

B-5