Table 10-3. CS5 Ratio Automatic/Manual Station Datapoints

Data-

point

Table

Module

Title and Function

De-

fault

AI0 - Auto Input

C256

5-4

AI0

Engineering Span - Enter a value, that when added to the
Engineering Zero value, will produce an upper range value in
engineering units that represents the Auto Input upper range
signal value.

100

C276

5-4

AI0

Engineering Zero - Enter a value that represents in
engineering units the Auto Input lower range signal value.

0

B269

5-4

AI0

Digital Filter Index - This is a first order filter that can be
applied to the Auto Input signal. See Table 5-4 for input
values.

3

L416

5-4

AI0

0-5 V Input - Enter a value that matches the voltage range of
the Auto Input signal. 1 = 0 - 5 V range; 0 = 1 - 5 V range.

0

L440

5-4

AI0

Square Root Signal - It is used if the Auto Input signal is a
squared value. 0 = input is already linear; 1 = square root to
restore linearization.

0

AI1 - Remote Ratio Input

C257

5-4

AI1

AI1 Engineering Span - Set to 100 by CS5; however, it can
be changed. Enter a value, that when added to the
Engineering Zero value, will produce an upper range value in
engineering units that represents the Remote Ratio Input
upper range signal value.

0

C277

5-4

AI1

Engineering Zero - Enter a value that represents in
engineering units the Remote Ratio Input lower range signal
value.

0

B270

5-4

AI1

Digital Filter Index - This is a first order filter that can be
applied to the Remote Ratio Input signal. See Table 5-4 for
input values.

3

L417

5-4

AI1

0-5 V Input - Enter a value that matches the signal voltage
range of the Remote Ratio Input signal. 1 = 0 - 5 V input
range; 0 = 1 - 5 V input range.

0

L441

5-4

AI1

Square Root Signal - It is used if the Remote Ratio input is a
squared signal value that must be linearized. 0 = input is
already linear; 1 = square root to restore linearization.

0

AI2 - Alarmed Variable

C258

5-4

AI2

Engineering Span - Enter a value, that when added to
Engineering Zero, will produce an upper range value in
engineering units that represents the Alarmed Variable upper
range signal value.

0

C278

5-4

AI2

Engineering Zero - Enter a value that represents in
engineering units the Alarmed Variable lower range signal
value.

0

B271

5-4

AI2

Digital Filter Index - This is a first order filter that can be
applied to the Alarmed Variable signal. See Table 5-4 for
input values.

3

1 of 3

Section 10. CS5 - Ratio Automatic/Manual Station