Table 5-9. controller modules (con0-3) – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instruction Manual User Manual

Page 163

background image

Table 5-9. Controller Modules (CON0-3)

Title

Definition

Atom

CON0

CON1

CON2

CON3

Default

Remote Setpoint Enable

When this parameter is set to a

1, the modified

Remote Setpoint is allowed to become the
setpoint value of the setpoint generator if the
Remote Switch (SWR) is set to a

1 by the R/L

push button or user program (F-TRAN, FCIM,
or FCS wire list). See also remote setpoint
modifiers Remote Setpoint Bias (B1) and
Remote Setpoint Ratio (K1).

RE

(0-3)

L115

L139

L163

L187

0

Setpoint Track Switch

See Setpoint Track Enable (STE).

SWSPT

(0-3)

L116

L140

L164

L188

0

Output Track Switch

See Output Track Enable (OTE).

SWOVT

(0-3)

L117

L141

L165

L189

0

SP Track Enable

When this parameter is configured to a

1, the

controller’s setpoint can be forced to match
Setpoint Track Value (STV) whenever the
Setpoint Track Switch (SWSPT) is a

0 . Based

on the input sources for STP and SWSPT,
process variable tracking, setpoint fallback,
and setpoint override, as well as other setpoint
schemes can be implemented in the local
setpoint generator.

STE

(0-3)

L118

L142

L166

L190

0

Output Track Enable

When this parameter is configured to a

1, the

controller’s setpoint can be forced to match
Output Track Value (OTV) whenever the
Output Track Switch (SWOVT) is a

0 . Based

on the input sources for OTV and SWOVT,
output fallback, and output override, as well as
other output schemes can be implemented in
the auto/manual switch generator.

OTE

(0-3)

L119

L143

L167

L191

0