Table 5-9. Controller Modules (CON0-3)
Title
Definition
Atom
CON0
CON1
CON2
CON3
Default
Remote Setpoint Enable
When this parameter is set to a
1, the modified
Remote Setpoint is allowed to become the
setpoint value of the setpoint generator if the
Remote Switch (SWR) is set to a
1 by the R/L
push button or user program (F-TRAN, FCIM,
or FCS wire list). See also remote setpoint
modifiers Remote Setpoint Bias (B1) and
Remote Setpoint Ratio (K1).
RE
(0-3)
L115
L139
L163
L187
0
Setpoint Track Switch
See Setpoint Track Enable (STE).
SWSPT
(0-3)
L116
L140
L164
L188
0
Output Track Switch
See Output Track Enable (OTE).
SWOVT
(0-3)
L117
L141
L165
L189
0
SP Track Enable
When this parameter is configured to a
1, the
controller’s setpoint can be forced to match
Setpoint Track Value (STV) whenever the
Setpoint Track Switch (SWSPT) is a
0 . Based
on the input sources for STP and SWSPT,
process variable tracking, setpoint fallback,
and setpoint override, as well as other setpoint
schemes can be implemented in the local
setpoint generator.
STE
(0-3)
L118
L142
L166
L190
0
Output Track Enable
When this parameter is configured to a
1, the
controller’s setpoint can be forced to match
Output Track Value (OTV) whenever the
Output Track Switch (SWOVT) is a
0 . Based
on the input sources for OTV and SWOVT,
output fallback, and output override, as well as
other output schemes can be implemented in
the auto/manual switch generator.
OTE
(0-3)
L119
L143
L167
L191
0