Table 14-3. CS40 Dual Two Loop Cascade Controller Datapoints

Data-

point

Table

Module

Title and Function

De-

fault

CON1

OUT (Setpoint from Loop 2 to Loop 4) (Cont)

C147

5-9

CON1

Manual Reset - It determines output valve position when the
controller Loop 2 is in Auto and the error = 0. It is mutually
exclusive with Reset Time.

50

L138

5-9

CON1

Auto Enable - Output is from the PID algorithm when set to 1
and the A/M push button is in Auto.

1

C115

5-9

CON1

Controller Span - Enter a value, that when added to the
Loop 2 Control Lower Range value, will produce the Control
upper range value in engineering units.

100

C152

5-9

CON1

Controller Lower Range - Enter a value that represents in
engineering units the Loop 2 Control lower range value.

0

AO1 - #2 Secondary Control Output (Loop 4)

L473

5-5

AO1

0-20 mA Output - 0 = 4-20 mA signal; 1 = 0-20 mA signal.
Enter a value to match the Loop 4 output valve requirements.

0

L192

5-9

CON3

Manual Fallback Disable - 0 = always power up Loop 4 in
manual; 1 = auto/manual selector unchanged at power up.

0

L194

5-9

CON3

Hard Manual Limit - 1 = apply output limits to the final output
of the Loop 4 Auto-Manual Generator. Affects both the
manual push buttons and the controller’s result. 0 = do not
apply limits.

1

C217

5-9

CON3

Output High Limit - Sets maximum Loop 4 output signal
value in engineering units.

100

C218

5-9

CON3

Output Low Limit - Sets minimum Loop 4 output signal value
in engineering units.

0

C226

5-9

CON3

Output Slew Rate - It is a rate limit applied to the output
value. When configured to a non-zero value, the output from
the Loop 4 Auto-Selector is only allowed to change by this
amount each scan time. A zero disables output slewing. It
does not affect manual operation.

0

CON 3 #2 Secondary Control Output (LOOP 4) Related Datapoints

C214

5-9

CON3

Proportional Band - Is the percent of error required to move
the Loop 4 output full scale for proportional action.

100

C215

5-9

CON3

Reset Time - Is the number of minutes per repeat of integral
action. It is mutually exclusive with Manual Reset.

0

C216

5-9

CON3

Rate Time - Represents the minutes proportional action is
advanced.

0

C219

5-9

CON3

Manual Reset - It determines output valve position when the
controller Loop 4 is in Auto and the error = 0. It is mutually
exclusive with Reset Time.

50

L178

5-9

CON3

Reverse Switch - 0 = Loop 4 output

if PV

; 1 = Loop 4

output

if PV

.

1

L186

5-9

CON3

Auto Enable - Output is from the PID algorithm when set to 1
and the A/M push button is in Auto.

1

C221

5-9

CON3

Remote Setpoint Ratio (K1) - See Remote Setpoint Bias (B1)
above.

1

5 of 7

Section 14. CS40 - Dual Two Loop Cascade Controller