Table 7-3. CS2 Analog Backup Controller Datapoints
Data-
point
Table
Module
Title and Function
De-
fault
DO1 - Backup Output Diverter
L025
5-7
DO1
When open, the controller output path is through the diverter
circuit diode to the final element. It is always in an opposite
state from DO0. (Not configurable.)
0
Alarms Related Datapoints
B335
5-9
CON0
Control Alarm Mode - Used to select one of six alarm types
or none. See Table 5-9 for details and examples.
1
C103
5-9
CON0
Alarm Limit 1 - Point in engineering units where an alarm is
triggered because the PV is not within the limit value set in
C103.
100
C104
5-9
CON0
Alarm Limit 2 - Point in engineering units where an alarm is
triggered because the PV is not within the limit value set in
C104.
0
C105
5-9
CON0
Alarm Dead Band - Sets the activation/deactivation gaps for
the alarm limit points. It is in engineering units.
2
Setpoint Related Datapoints
C114
5-9
CON0
Control Zone - A gap on both sides of setpoint. When PV is
within this gap, the proportional and integral output changes
are suppressed. Derivative output is unaffected.
0
C125
5-9
CON0
Setpoint High Limit - It is the maximum control setpoint value
allowed.
100
C126
5-9
CON0
Setpoint Low Limit - It is the minimum control setpoint value
allowed.
0
C117
5-9
CON0
Setpoint Slew Rate - It is a rate limit applied to the setpoint.
When configured to a non-zero value, the setpoint used in
the PID algorithm is only allowed to change by this amount
each scan time. The final value of the setpoint always
appears on the units display. A zero disables setpoint
slewing.
0
Miscellaneous Datapoints
A000
5-9
CON0
Tagname - Assignable 10 character name.
CON-
0
A001
5-9
CON0
Engineering Units - Assignable 10 character designator.
PER-
CENT
L109
5-9
CON0
Reverse Valve - Bottom of display output valve action
indicators: 1 = [O] [C] display order, 0 = [C] [O] display order.
0
3 of 3
Section 7. CS2 - Analog Backup Controller
7-7