Table 5-9. Controller Modules (CON0-3)
Title
Definition
Atom
CON0
CON1
CON2
CON3
Default
Setpoint Mode
This parameter specifies how the setpoint
increase and decrease push buttons function
when the controller is in remote:
0 - STD (push buttons have no effect).
1 - K-SP (push buttons adjust Remote Setpoint
Ratio, K1 - C113, etc.).
2 - B-SP (push buttons adjust Remote Setpoint
Bias, B1 - C112, etc.).
SPM
(0-3)
B338
B343
B348
B353
0
Control Display Mode
This parameter controls the type of point
display that is used with the CON module.
0 - STD (Standard PID).
1 - IND (Indicator).
2 - LDR (Manual Loader).
3 - RCTRL (Ratio Controller).
4 - SEL (Automatic/Manual Station).
5 - RSEL (Ratio Automatic/Manual Station).
CDM
(0-3)
B339
B344
B349
B354
0
SP Track Status
1 indicates the setpoint comes from Setpoint
Track Value (STV).
0 indicates the setpoint
comes from the setpoint push buttons or is a
Remote Setpoint (RSP) dependent on the
value of Remote Status (RMT).
SPTS
(0-3)
L104
L128
L152
L176
0
Output Track Status
1 indicates the output comes from the Output
Track Value (OTV). A
0 indicates the output
comes from the output push buttons or the
Control Output (CO). Output Track Status is
dependent on the value of Auto Status (AUT).
OVTS
(0-3)
L105
L129
L153
L177
0
Reverse Switch
0 - DIR (When set to a
0 , the controller output
increases as the process variable increases).
1 - REV (When set to a
1 , the controller output
decreases as the process variable increases).
RSW
(0-3)
L106
L130
L154
L178
1
3 of 9
5-
1
6