Page 264

background image

Table 14-1. CS40 Control Signals

Control

Signal

Definition

Cord

Set

ITB

Rear

Term

Board

Signal

DO1 - #2
Secondary
Process
Alarms

This contact is closed when the #2 Secondary
Process Variable value is not within the C211
and C212 datapoint values (#2 Secondary
Alarm Limits 1 and 2); otherwise, the contact is
open.

TB2-7 (+)
TB2-8 (-)

18 (+)
17 (-)

DO1
PC

14.3 CS40 STANDARD DISPLAYS

Loading CS40 preconfigures the System Module display list for ten displays. The ten displays are
listed in Table 14-2 with appropriate reference sections, figure numbers, and configuration tables.
A configuration table is not listed for the Four Loop CON0 - CON3 display, as that information is
provided in this section. To configure the Horizontal Trend, System Status, and Status Module dis-
plays, reference the Section 4 and Section 5 information listed in the table. The Alarm Summary
display does not have to be configured; however, it is described and illustrated in Section 4.

Table 14-2. CS40 Standard Displays

Title

See

Section

Section 4

Figure

Section 5

Table

Four Loop CON0 - CON3

4.10

4-15

Single Loop CON0 with Horizontal Trend

4.5

4-10 sheet 2

5-9 and 5-12

Single Loop CON1 with Horizontal Trend

4.5

4-10 sheet 2

5-9 and 5-12

Single Loop CON2 with Horizontal Trend

4.5

4-10 sheet 2

5-9 and 5-12

Single Loop CON3 with Horizontal Trend

4.5

4-10 sheet 2

5-9 and 5-12

Alarm Summary

4.1

4-1

System Status

4.2

4-2

5-15

Status Module 0

4.7

4-12

5-10

Status Module 1

4.7

4-12

5-10

Four Loop CON0 - CON3

4.10

4-15

14.4 CS40 DATAPOINT CONFIGURATION SELECTIONS

See Figure 14-2 and Table 14-3 to configure datapoints for CS40 - Dual Two Loop Cascade Con-
troller. Table 14-3 also lists the Section 5 modules that can be referenced for more detailed defini-
tions of the datapoints when required. A datapoint does not have to be configured if the
default value listed in Table 14-3 is appropriate for the process application.
Loading CS40 in-
itializes the Engineering Spans to 100 for AIs 1-3 (C257, C258, and C259). Also, C076 (Math A -
K1) is set to 1.0, C077 (Math A - K2) is set to -1.0, C085 (Math D - K1) is set to 1.0, and C086
(Math D - K2) is set to -1.0. The CON0

OUT and CON1

OUT signals, which are the secondary set-

point inputs, must be properly scaled by configuring datapoints C184 (B1) and C185 (K1) for the #1
Secondary Control Output; and by configuring C220 (B1) and C221 (K1) for the #2 Secondary Con-
trol Output. These datapoints are listed in Table 14-3 under their respective CON

OUT Datapoints.

2 of 2

Section 14. CS40 - Dual Two Loop Cascade Controller

14-3