Table 14-3. CS40 Dual Two Loop Cascade Controller Datapoints
Data-
point
Table
Module
Title and Function
De-
fault
Setpoint Related Datapoints (Loops 1, 2, 3, 4)
C114,
C150,
C186,
C222
5-9
CON0,
CON1,
CON2,
CON3
Control Zone - A gap on both sides of setpoint. When PV is
within this gap, the proportional and integral output changes
are suppressed. Derivative output is unaffected.
0
C125,
C161,
C197,
C233
5-9
CON0,
CON1,
CON2,
CON3
Setpoint High Limit - It is the maximum setpoint value
allowed.
100
C126,
C162,
C198,
C234
5-9
CON0,
CON1,
CON2,
CON3
Setpoint Low Limit - It is the minimum setpoint value allowed.
0
C117,
C153,
C189,
C225
5-9
CON0,
CON1,
CON2,
CON3
Setpoint Slew Rate - It is a rate limit applied to the setpoint.
When configured to a non-zero value, the setpoint used in
the PID algorithm is only allowed to change by this amount
each scan time. The final value of the setpoint always
appears on the units display. A zero disables setpoint
slewing.
0
Miscellaneous Datapoints (Loops 1, 2, 3, 4)
A008
Unit Tagname - Assignable 10 character name, e.g.,
MC5000.
A000,
A002,
A004,
A006
5-9
CON0,
CON1,
CON2,
CON3
Tagname - Assignable 10 character name.
CON-
0, 1,
2, 3
A001,
A003,
A005,
A007
5-9
CON0,
CON1,
CON2,
CON3
Engineering Units - Assignable 10 character designator.
(Appears on Trend displays.)
PER-
CENT
7 of 7
Section 14. CS40 - Dual Two Loop Cascade Controller