Table 14-3. CS40 Dual Two Loop Cascade Controller Datapoints

Data-

point

Table

Module

Title and Function

De-

fault

AI0 - #1 Primary Process Variable

C256

5-4

AI0

Engineering Span - Enter a value, that when added to the
Engineering Zero value, will produce an upper range value in
engineering units that represents the #1Primary Variable
transducer upper range signal value.

100

C276

5-4

AI0

Engineering Zero - Enter a value that represents in
engineering units the #1 Primary Variable transducer lower
range signal value.

0

B269

5-4

AI0

Digital Filter Index - This is a first order filter that can be
applied to the #1 Primary Variable transducer signal. See
Table 5-4 for input values.

3

L416

5-4

AI0

0-5 V Input - Enter a value that matches the signal voltage
range of the #1 Primary Variable transducer. 1 = 0 - 5 V
range; 0 = 1 - 5 V range.

0

L440

5-4

AI0

Square Root Signal - It is used if the #1 Primary Variable
transducer is a nonlinear differential pressure (DP) cell that
provides a squared signal value. 0 = input is already linear;
1 = square root to restore linearization.

0

AI1 - #2 Primary Process Variable

C257

5-4

AI1

Engineering Span - Enter a value, that when added to
Engineering Zero, will produce an upper range value in
engineering units that represents the #2 Primary Variable
transducer upper range signal value.

0

C277

5-4

AI1

Engineering Zero - Enter a value that represents in
engineering units the #2 Primary Variable transducer lower
range signal value.

0

B270

5-4

AI1

Digital Filter Index - This is a first order filter that can be
applied to the #2 Primary Variable transducer signal. See
Table 5-4 for input values.

3

L417

5-4

AI1

0-5 V Input - Enter a value that matches the signal voltage
range of the #2 Primary Variable transducer. 1 = 0 - 5 V
range; 0 = 1 - 5 V range.

0

L441

5-4

AI1

Square Root Signal - It is used if the #2 Primary Variable
transducer is a nonlinear differential pressure (DP) cell that
provides a squared signal value. 0 = input is already linear;
1 = square root to restore linearization.

0

AI2 - #1 Secondary Process Variable

C258

5-4

AI2

Engineering Span - Set to 100 by CS40; however, it can be
changed. Enter a value, that when added to the Engineering
Zero value, will produce an upper range value in engineering
units that represents the #1 Secondary Variable transducer
upper range signal value.

0

C278

5-4

AI2

Engineering Zero - Enter a value that represents in
engineering units the #1 Secondary Variable transducer
lower range signal value.

0

1 of 7

Section 14. CS40 - Dual Two Loop Cascade Controller

14-7