Micromod MOD: 30ML Quick Reference Guide User Manual
Reference card mod 30ml™ controller, Controller front panel
Reference Card
MOD 30ML™ Controller
MicroMod Automation, Inc.
75 Town Centre Dr.
Rochester, NY 14623 USA
Tel: (585) 321-9200
Fax: (585) 321-9291
928 Jaymor Road, Suite B-120
Southampton, PA 18966 USA
Tel: (215) 355-4377
Fax: (215) 355-4378
MicroMod Automation S. de R.L.
Mexico
Tel: (55) 57373402
Fax: (55) 57373402
WWW.MICROMODAUTOMATION.COM
Controller Front Panel
Alarm Light
Alarm Scroll
Key
Loop Tag
Display Scroll
or Escape
Line 2
Manual Key
Auto Key
Remote/
Local Key
Scroll Key
Up Key
/ = immediate
entry.
No slash =
Entry [ENT]
required.
Down Key
Process
Variable
Bar Graph
(Line 2)
Set-Point
Variable
Bar Graph
(Line 6)
Output
Bar Graph
(Line 6)
Line 1: Loop Tag Display
Line 2: Process Value and engineering units label.
Line 3: MAN = Manual
AUT = Auto
UAK = Unacknowledged Alarm
ACT = Active Acknowledged Alarm
UBQ = Unacknowledged Bad Quality
ABQ = Active Bad Quality
CLR = Acknowledged Alarm Clear
LHD = Local Hold (service switch set)
Line 4: LOC = Local
REM = Remote
TRK = Track
RET = Return (from alarm display)
PRV = Previous Step (Tune and Setup)
Line 5: OP = Output value on Line 6
SP = Set-Point value on Line 6
RA = Ratio value on Line 6
BI = Bias value on Line 6
FF = Feed Forward value on Line 6
RSP = Remote Set-Point value on Line 6
TUN = Alarm or Control Tune request
ENT = Enter Value (flashes while active)
NXT = Next Step (Tune and Setup)
Line 6: Line 5 value or Tune and Setup choices.
Service / Run Switch
RUN is the normal
operating position.
SERV. position puts
instrument in local hold
state (LHD) and only
*DEVICE* displays are
active.
RS-232 Port (if configured)
requires Application Builder.
READ/WRITE
READ ONLY
NORMAL
MODULE
LOAD
From Main Database to Memory
Module
1. Set switches to Read/Write and
Module Load.
2. Power up instrument.
3. UPLOAD? is displayed . Press
Up or Down key and Enter (scroll
key).
4. UPL DONE SET WP? is
displayed. Upload done. Set Write
Protect? by pressing Up key and
entering. Otherwise, skip this step.
5. Power down instrument and set
switches to Normal and
Read/Write or Read Only.
6. Power up instrument.
From Memory Module to Main Database
1. Set switches to Read/Write or Read Only and Normal.
2. Power up instrument.
The instrument automatically attempts a download
Line 1 / Line 2 Display
Line 6 Display / Entry
Entry point.
NONE, OUT CH 1, OUT CH 2, S01 to S11.
Only outputs not used elsewhere are listed.
0% of output range.
100% of output range.
Float 0 = X, Float 1 = X.X, Float 2 = X.XX,
and so forth to Float 6 = X.XXXXXX
Value determines lower output limit.
Value determines upper output limit.
Previous, Preset.
Any initial output value.
Exit point.
Entry point. Alarms.
Entry point. Process Value Alarms.
NONE, HIGHHIGH (>=), HIGH (>=),
LO (<=), LOW LOW (<=).
Value where input will cause the alarm to
become active.
Absolute offset to clear alarm.
0 = Suppress Unacknowledge, 1 to 255
defines priority level (1 is highest).
NONE, S01 to S11. Only unused shown.
Repeat Process Value Alarms setup for
2, 3 and 4.
Exit point. Process alarms.
Entry point. Deviation Alarms.
NONE, HIGHHIGH (>=), HIGH (>=),
LO (<=), LOW LOW (<=).
Value where input will cause the alarm to
become active.
Absolute offset to clear alarm.
0 = Suppress Unacknowledge, 1 to 255
defines priority level (1 is highest).
NONE, S01 to S11. Only unused shown.
Repeat setup for Deviation Alarm 2.
Exit point. Deviation Alarms.
Entry point. Output Alarms.
NONE, HIGHHIGH (>=), HIGH (>=),
LO (<=), LOW LOW (<=).
Value where input will cause the alarm to
become active.
Absolute offset to clear alarm.
0 = Suppress Unacknowledge, 1 to 255
defines priority level (1 is highest).
NONE, S01 to S11. Only unused shown.
Repeat setup for Output Alarm 2.
Exit point. Output Alarms.
Exit point. Alarms.
Exit point. Compound List (return to General
Template setup for next compound).
CTAG01 OUTPT
Output
OUTPUT SLOT
Output Slot Position
OUTPUT LO SIGNL
Output Low Signal
COMPOUND
OUTPUT HI SIGNL
Output High Signal
OUTPUT DISP FMT
Output Display Format
OUTPUT LO LIMIT
Output Low Limit
OUTPUT HI LIMIT
Output High Limit
RESTART TYPE
Output Restart Type
OUTPUT INIT VAL
Output Initial Value
CTAG01 ALARMS
Alarms
PV ALARMS
PV ALM 1 TYPE
Process Val. 1 Alarm Type
PV ALM 1 TRIP VAL
Trip Value
PV ALM 1 HYSTRSIS
Hysteresis
PV ALM 1 PRIORITY
Priority
ALARMS
DEVIATN ALARMS
DEVALM 1 TYPE
Deviation 1 Alarm Type
DEVALM 1 TRIP VAL
Trip Value
DEVALM 1 HYSTRSIS
Hysteresis
DEVALM 1 PRIORITY
Priority
PV ALM 1 DIG OUT
Digital Output
ALARMS
DEVALM 1 DIG OUT
Digital Output
OUTPUT ALARMS
OUTALM 1 TYPE
Output 1 Alarm Type
OUTALM 1 TRIP VAL
Trip Value
OUTALM 1 HYSTRSIS
Hysteresis
OUTALM 1 PRIORITY
Priority
ALARMS
OUTALM 1 DIG OUT
Digital Output
COMPOUND
COMPOUND LIST
The Company's policy is one of continuous
improvement and the right is reserved to modify
specifications without notice.
© 2004, MicroMod Automation Printed in USA
QRG-1800R
Issue 2
Line Display Description
Memory Module
UPLOAD:
DOWNLOAD: