B.1.5 CALCULATING DATA ADDRESSES

If communications software must be generated to accommodate unique Datalink applications re-
quirements, then the controller memory address scheme must be known for proper data bit (e.g., L
data type) and data byte (e.g., B, C, H, and A data types) memory location determination.

Note: Numbers used in this section that are expressed in hexadecimal notation (base 16) are iden-
tified with a subscript

H

after the number.

This memory address scheme applies only if a

6 is in memory address location 8002

H

. Memory

address location 8002

H

must be read and if it contains a

6, then the address scheme that is de-

scribed in Table B-3 should be applied for this controller.

Table B-3. Controller Memory Address Scheme

Data

Type

Base

Memory

Address

Byte

Size

Data Format

Address Calculation Algorithm

B

200

H

1

Represents a positive integer
with values from 0 to 255.

Address = B Base + (B Number)
= 200

H

+ (B Number)

Address example: B012 location
= 200

H

+ 12

D

= 200

H

+ C

H

= 20C

H

L

500

H

1 Bit

A single binary bit with a logical
value of 0 or 1. L datapoints
are packed 8 to a byte.

Address = L Base + (L Number/8)
= 500

H

+ (L Number/8)

Remainder = bit position in byte
Address example: L014 location
= 500

H

+ 14/8 = 501

H

, bit 6

(remainder).

C

600

H

3

Represents floating point values
that have a resolution of one
part in 32,768 (15 bits) and a
dynamic range of

±

10

38

. The

first two bytes represent a 2’s
complement notation in
fractional form (2

-n

) whose

absolute value is between 0.5
and 0.9999. The third byte is
the power of 2 in 2’s
complement notation. Floating
point example:
64

H

00

H

07

H

= 100

D

(Decimal)

64

H

= 0110 0100, fractional

binary weights left to right are 0
= 2’s complement positive,
1 = 2

-1

= 1/2 = 0.5, 1 = 2

-2

=

1/4 = 0.25, 0=0, 0=0, 1 = 2

-5

=

1/32 = 0.03125, 0=0, and 0=0.
64

H

= 0.5+0.25+0.03125 =

0.78125. 07

H

= 128

D

. 128

D

X

0.78125

D

= 100.

Address = C Base + (3 X C Number)
= 600

H

+ (3 X C Number)

Address example: C011 location
600

H

+ (3 X 11) = 600

H

+ 33

D

= 600

H

+ 21

H

= 621

H

.