UPS Controller

D-3

On: Indicates that the contact is closed.

Off: Indicates that the contact is open.

Note 1: Use a UPS that can normally supply power from the battery at least 10 to 60 seconds after *BTL is turned on.

Note 2: Use a UPS that can normally supply power from the battery within 2 seconds of a momentary commercial power interruption

even if *ACOFF is not turned on.

*ACOFF

Indicates that a power failure has occurred in the
commercial power supply connected to the UPS.

9

Normal state: Off
Abnormal state: On
(Note 2)

SG

Signal ground

5

ER
(Equipment Ready)

Indicates that the server is operating

1

Do not connect
anything to this pin.

TABLE D-1

Signal Line Definitions (Continued)

Signal name

Definitions

Pin number