Chapter 7

I/O Unit (IOU) Replacement

7-9

SPARC Enterprise M4000/M5000/M8000/M9000 Servers Dynamic Reconfiguration
(DR) User’s Guide
. For details on how to log in to XSCF, see the SPARC
Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF User’s Guide
.

Hot replacement:

From the terminal connected to the XSCF, select all the domains that have been
recognized in

Step 2

as including the CMU to be replaced, and execute the

poweroff -d

command to shut down the domains. (The IOU status can be

checked by executing the showboards command.)

Domain administrator authority is required for executing this command. For
details on how to log in to XSCF, see the SPARC Enterprise
M3000/M4000/M5000/M8000/M9000 Servers XSCF User’s Guide
.

4. Use the maintenance menu to select the replacement target IOU. (The

maintenance menu is used up to

Step 11

.)

The fieldeng permission is required for executing this command.

a. From the console that is connected to XSCF, log in to XSCF, and execute the

replacefru

command.As shown in

FIGURE 7-6

, the initial page of the

maintenance menu is displayed.

FIGURE 7-6

Initial Page of the Maintenance Menu

Note –

DDC_A is displayed only for the M8000.

b. From the replacement parts list in the maintenance menu, select 1,

"CMU/IOU."

---------------------------------------------------

Maintenance/Replacement Menu

Please select a type of FRU to be replaced.

1. CMU/IOU(CPU Memory Board Unit/IO Unit)

2. FAN(Fan Unit)

3. PSU(Power Supply Unit)

4. XSCFU(Extended System Control Facility Unit)

5. DDC_A(DDC for BP_A)

---------------------------------------------------

Select [1-5|c:cancel] :