20-20

SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009

FIGURE 20-12

Removing the PSUBP (Front of the M9000)

9. Place the removed BP on an antistatic conductive mat.

10. Mount the replacement BP by following the removal instructions in

Step 7

and

Step 8

in reverse order. Align the holes by the side of the thumb screws of the

PSUBP with the two guide pins in the cabinet.

Note –

To mount a FAN BP on a fan shelf that has a guide pin, align the FAN BP

with the guide pin during mounting.

Caution –

Be sure not to hit connector parts of the BP against anything. Otherwise,

the connection pins may be seriously damaged.

11. Switch on all main line switches for the AC section (ACS) in the power supply

system.

12. Confirm that the XSCF STANDBY LED (green) on the operator panel remains

lit. If it is blinking, wait until it remains lit.