SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009

12. Start (turn on power) all domains together. Take either of the following two

actions:

Press and hold down (for less than four seconds) the POWER switch on the
operator panel.

From a console that is connected to XSCF, execute the poweron -a command
of XSCF.

The power to all the domains is turned on, and then the power-on self test (POST)
is executed. When ok prompt displayed on the console of relevant domain, POST
is completed.

For details of the power-on operation, see

Section 4.4.2, “Powering the Server On”

on page 4-19

, and the SPARC Enterprise M3000/M4000/M5000/M8000/M9000

Servers XSCF User’s Guide.

13. Confirm that the replacement components are normal by using the

showhardconf

or showstatus command of XSCF.

Unless "*" is displayed for the replacement ACS, it is operating normally.

For details of the showhardconf command and showstatus command, see the
SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF User’s Guide,
the SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF Reference
Manual
, or the man page.

Note –

The showstatus command displays information on degraded components.

14. Restore the original mode switch setting on the operator panel.

Note –

When the maintenance work is completed, be sure to confirm the mode

switch setting and return the switch to Locked.

15. Close the door on the server, and lock it.