FUJITSU SPARC ENTERPRISE M8000 User Manual
Page 251

Chapter 10
Operator Panel Replacement
10-7
■
Press and hold down (for less than four seconds) the POWER switch on the
operator panel.
■
From a console that is connected to XSCF, execute the poweron -a command
of XSCF.
The power to all the domains is turned on, and then the power-on self test (POST)
is executed. When ok prompt displayed on the console of relevant domain, POST
is completed.
For details of the power-on operation, see
Section 4.4.2, “Powering the Server On”
, and the SPARC Enterprise M3000/M4000/M5000/M8000/M9000
Servers XSCF User’s Guide.
16. Confirm that the replaced components are normal by using the showhardconf
or showstatus command of XSCF.
Unless "*" is displayed for the replacement OPNL, it is operating normally.
For details of the showhardconf command and showstatus command, see the
SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF User’s Guide,
the SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF Reference
Manual, or the man page.
Note –
The showstatus command displays information on degraded components.
17. Restore the original mode switch setting on the operator panel.
Note –
When the maintenance work is completed, be sure to confirm the mode
switch setting and return the switch to Locked.
18. Close the door on the server, and lock it.