6-6

SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009

4. Collect an XSCF snapshot to archive system status prior to upgrade.

This will be help in case any problem occurred in this procedure.

5. Update the XCP version.

For the firmware updating procedures, see the SPARC Enterprise
M3000/M4000/M5000/M8000/M9000 Servers XSCF User’s Guide
.

6. After updating the XCP, reset the XSCF.

7. After resetting the XSCF, log in to the XSCF again.

8. Mount the CPU module (CPUM) on the CMU for add-on.

For the procedure, see the description about the CPU module installation in

Section 6.5.1, “Replacing a CPU Module” on page 6-27

.

9. Mount the CMU, described in

Step 8

, on the server.

a. Executing the addfru(8) command and select “CMU/IOU” from the

maintenance menu.

b. Perform the operation according to the instructions displayed in the

maintenance menu, referring to

Section 6.3, “Active Replacement and Hot

Replacement” on page 6-12

.

Note –

Do not fail to execute the diagnosis of newly mounted CMU in the

maintenance menu of addfru(8) command.

10. Confirm that the mounted CPU module has been recognized by the server, and

the error indicator asterisk (*) is not displayed.

11. Confirm no abnormality occurred by using showlogs error -v and

showstatus

(8) commands.

12. Move the key position on the operator panel from Service to Locked.

XSCF> snapshot -t

user@host:directory

XSCF> rebootxscf

XSCF> addfru

XSCF> showhardconf -M

XSCF> showlogs error -v

XSCF> showstatus