Chapter 22

Media Backplane Replacement

22-9

From a console that is connected to XSCF, execute the poweron -a command
of XSCF.

The power to all the domains is turned on, and then the power-on self test (POST)
is executed. When ok prompt displayed on the console of relevant domain, POST
is completed.

For details of the power-on operation, see

Section 4.4.2, “Powering the Server On”

on page 4-19

, and the SPARC Enterprise M3000/M4000/M5000/M8000/M9000

Servers XSCF User’s Guide.

14. Restore the original mode switch setting on the operator panel.

Note –

When the maintenance work is completed, be sure to confirm the mode

switch setting and return the switch to Locked.

15. Close the door on the server, and lock it.