Input fusing requirements, Input fusing requirements -11 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 69
Mounting and Wiring Information Specific to Frames B, C, D, E, F, G, and H
4-11
Input Fusing Requirements
The following are the input fusing requirements for frames B, C, D,
E, F, G, and H.
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
European Installations
North American
Installations
Drive Catalog
Number
kW (HP)
Rating
200 – 240V
Rating
380 – 480V
Rating
500 – 600V
Rating
The recommended fuse is
Class gG, general industrial
applications and motor circuit
protection.
BS88 (British Standard) Parts 1
& 2*, EN60269-1, Parts 1 & 2,
type gG or equivalent should be
used for these drives. Fuses
that meet BS88 Parts 1 & 2 are
acceptable for Frames A – F.
* Typical designations include,
but may not be limited to the
following:
Parts 1 & 2: AC, AD, BC, BD,
CD, DD, ED, EFS, EF, FF, FG,
GF, GG, GH.
UL requirements specify
that UL Class CC, T, or J
1
fuses must be used for all
drives in this section*.
* Typical designations
include:
Type CC: KTK, FNQ-R
Type J: JKS, LPJ
Type T: JJS, JJN
UL requirements specify
that UL Class CC, T, or J
fuses must be used for all
drives in this section*.
* Typical designations
include:
Type CC: KTK, FNQ-R
Type J: JKS, LPJ
Type T: JJS, JJN
1336E-_ _ 007
5.5 (7.5)
40A
20A
15A
1336E-_ _ 010
7.5 (10)
50A
30A
20A
1336E-_ _ 015
11 (15)
70A
35A
25A
1336E-_ _ 020
15 (20)
100A
45A
35A
1336E-_ _ 025
18.5 (25)
100A
60A
40A
1336E-_ _ 030
22 (30)
125A
70A
50A
1336E-_ _ X040
30 (40)
150A
80A
60A
1336E-_ _ 040
30 (40)
150A
80A
60A
1336E-_ _ 050
37 (50)
200A
100A
80A
1336E-_ _ X060
45 (60)
—
100A
—
1336E-_ _ 060
45 (60)
250A
125A
90A
1336E-_ _ 075
56 (75)
300A
150A
110A
1336E-_ _ 100
75 (100)
400A
200A
150A
1336E-_ _ 125
93 (125)
450A
250A
175A
1336E-_ _ X150
112 (150)
—
250A
—
1336E-_ _ 150
112 (150)
—
300A
225A
1336E-_ _ 200
149 (200)
—
400A
350A
1336E-_ _ 250
187 (250)
—
450A
400A
1336E-_ _ X300
224 (300)
—
—
400A
The recommended fuse is
Class gG, general industrial
applications and motor circuit
protection.
BS88 (British Standard) Part 4,
EN60269-1, Part 4*, type gG
semiconductor fuses or
equivalent should be used for
these drives. G Frame drives
require semiconductor fuses
and should be fused with Part 4
fuses.
* Typical designations include,
but may not be limited to the
following:
Part 4: CT, ET, FE, EET, FEE,
RFEE, FM, FMM.
Bussmann FWP/Gould
Shawmut A-70Q or QS
semiconductor type fuses
must be used for all drives
in this section.
1336E-_ _ 300
224 (300)
—
500A
400A
1336E-_ _ P300
2
224 (300)
—
500A
—
1336E-_ _ 350
224 (300)
—
600A
450A
1336E-_ _ P350
261 (350)
—
600A
—
2
1336E-_ _ 400
298 (400)
—
600A
500A
1336E-_ _ P400
298 (400)
—
600A
—
2
1336E-_ _ 450
336 (450)
—
800A
600A
1336E-_ _ P450
336 (450)
—
700A
—
2
1336E-_ _ 500
373 (500)
—
800A
800A
1336E-_ _ 600
448 (600)
—
900A
800A
1336E-_ _ 650
485 (650)
—
—
800A
1336E-_ _ 700C
522 (700)
—
600A
3
1336E-_ _ 800C
597 (800)
—
700A
1 Both fast acting and slow blow are acceptable.
2 Fuses are supplied with F and H Frame drives.
3 Two fuses in parallel are required.