34
Speed Ref 5
Enter the speed reference that the drive should use when speed
reference 5 is selected in Logic Input Sts (parameter 14).
Parameter number
File:group
Control:Speed Reference
Parameter type
linkable destination
Display
±x.x rpm
Factory default
+0.0 rpm
Minimum value
-8 x base motor speed rpm
Maximum value
+8 x base motor speed rpm
Conversion
4096 = base motor speed
35
Speed Ref 6
Enter the speed reference that the drive should use when speed
reference 6 is selected in Logic Input Sts (parameter 14).
Parameter number
File:group
Control:Speed Reference
Parameter type
linkable destination
Display
±x.x rpm
Factory default
+0.0 rpm
Minimum value
-8 x base motor speed rpm
Maximum value
+8 x base motor speed rpm
Conversion
4096 = base motor speed
36
Speed Ref 7
Enter the speed reference that the drive should use when speed
reference 7 is selected in Logic Input Sts (parameter 14).
Parameter number
File:group
Control:Speed Reference
Parameter type
linkable destination
Display
±x.x rpm
Factory default
+0.0 rpm
Minimum value
-8 x base motor speed rpm
Maximum value
+8 x base motor speed rpm
Conversion
4096 = base motor speed
37
Speed Scale 7
Enter the gain multiplier used to scale Speed Ref 7
(parameter 36).
Parameter number
File:group
Control:Speed Reference
Parameter type
linkable destination
Display
±x.xxxx
Factory default
+1.0000
Minimum value
-3.9999
Maximum value
+3.9999
Conversion
8192 = 1.0000
38
Jog Speed 1
Enter the speed reference that the drive should use when Jog 1
is selected in Logic Input Sts (parameter 14).
Parameter number
File:group
Control:Speed Reference
Parameter type
linkable destination
Display
±x.x rpm
Factory default
+100.0 rpm
Minimum value
-8 x base motor speed rpm
Maximum value
+8 x base motor speed rpm
Conversion
4096 = base motor speed
39
Jog Speed 2
Enter the speed reference that the drive should use when Jog 2
is selected in Logic Input Sts (parameter 14).
Parameter number
File:group
Control:Speed Reference
Parameter type
linkable destination
Display
±x.x rpm
Factory default
+0.0 rpm
Minimum value
-8 x base motor speed rpm
Maximum value
+8 x base motor speed rpm
Conversion
4096 = base motor speed