100
An In 2 Offset
Use An In 2 Offset to set the offset applied to the raw analog
value of analog input 2 before the scale factor is applied. This lets
you shift the range of the analog input.
Parameter number
File:group
Interface/Comm:Analog Inputs
Parameter type
linkable destination
Display
±x.xxx volts
Factory default
0.000 volts
Minimum value
-19.980 volts
Maximum value
+19.980 volts
Conversion
205 = 1.000
101
An In 2 Scale
Use An In 2 Scale to set the scale factor or gain for analog
input 2. The value of analog input 2 is converted to +2048 and
then the scale is applied. This provides an effective digital range
of
±32767.
Parameter number
File:group
Interface/Comm:Analog Inputs
Parameter type
linkable destination
Display
±x.xxx
Factory default
+2.000
Minimum value
-16.000
Maximum value
+16.000
Conversion
2048 = 1.000
102
mA Input Value
Use mA Input Value to view the converted analog value of the
milli amp input.
Parameter number
File:group
Interface/Comm:Analog Inputs
Parameter type
source
Display
±x
Factory default
not applicable
Minimum value
-32767
Maximum value
+32767
Conversion
1 = 1
103
mA Input Offset
Use mA Input Offset to set the offset applied to the raw analog
value of the milli amp input before the scale factor is applied. This
lets you shift the range of the analog input.
Parameter number
File:group
Interface/Comm:Analog Inputs
Parameter type
linkable destination
Display
±x.xxx mA
Factory default
+0.000 mA
Minimum value
-32.000 mA
Maximum value
+32.000 mA
Conversion
128 = 1.000
104
mA Input Scale
Enter the scale factor or gain for the milli amp input. The milli amp
input is converted to +2048 and then the scale is applied. This
provides an effective digital range of
±32767.
Parameter number
File:group
Interface/Comm:Analog Inputs
Parameter type
linkable destination
Display
±x.xxx
Factory default
+2.000
Minimum value
-16.000
Maximum value
+16.000
Conversion
2048 = 1.000
105
An Out 1 Value
Use An Out 1 Value to convert a +32767 digital value to a +10
volt output. This is the value of the analog output number 1.
Parameter number
File:group
Interface/Comm:Analog Outputs
Parameter type
linkable destination
Display
±x
Factory default
+0
Minimum value
-32767
Maximum value
+32767
Conversion
1 = 1