Setting up the analog i/o parameters for scanport – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 138
8-14
Using the SCANport Capabilities
Setting Up the Analog I/O
Parameters for SCANport
The following figure shows the six SCANports that are available for
use with the SCANport analog I/O and the drive parameters that you
can use to control this data.
This message:
Lets you:
Continuous Parameter Value Read
Read a continuous list of parameters beginning with the starting parameter number.
Continuous Parameter Value Write
Write to a continuous list of parameters beginning with the starting parameter number.
Scattered Parameter Value Read
Read a scattered list of parameters.
Scattered Parameter Value Write
Write to a scattered list of parameters and return the status of each parameter.
Continuous Parameter Link Read
Read a continuous list of links beginning with the starting parameter number.
Continuous Parameter Link Write
Write a continuous list of links beginning with the starting parameter number.
Scattered Parameter Link Read
Read a scattered list of parameter links.
Scattered Parameter Link Write
Write a scattered list of parameter links.
Read Product Number
Request the product number from a device.
Product Text String Read
Request the product text from a device.
Last Parameter Number Read
Request the last parameter number.
EE Command Write
Activate the specified EE function.
Read Full Parameter
Request all known attributes for the requested parameters.
Parameter Value Read
Request the value for a specific parameter.
Parameter Value Write
Write a value to a specific parameter.
Fault Command Write
Clear faults, clear the fault queue, and reset.
Fault Queue Size
Read the number of fault entries allowed in the fault queue.
Trip Fault Read
Request which fault queue entry tripped the drive.
Fault Queue Entry Read Full
Read the contents of the specified fault queue entry.
Warning Command Write
Clear faults and clear the warning queue.
Warning Queue Size
Read the number of fault entries allowed in the warning queue.
Warning Queue Entry Read Full
Read the contents of the specified warning queue entry.
Link Command Write
Clear all links.
Read Parameter Link
Request the parameter link information for a specific parameter.
Write Parameter Link
Write the parameter link information for a specific parameter.
Product Diagnostic Value
Access a simple parameter link checksum.
file:
Interface/Comm
group:
SCANport Analog
1
2
3
4
5
6
SP An In1 Sel (Par 133)
139
134
SP An In1 Value
1
2
3
4
5
6
SP An Output
SP An In1 Scale (Par 135)
SP An In2 Sel (Par 136)
137
SP An In2 Value
SP An In2 Scale (Par 138)
1
2
3
4
5
6