170 vd max, 171 vq max, 172 trans dgn config – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 249: 173 autotune/dgn sel
![background image](/manuals/578736/249/background.png)
Parameters
11-51
170
Vd Max
Use Vd Max to view the maximum D axis voltage allowed on the
motor. The auto-tune routine calculates the value of Vd Max. You
should not change this value.
Vd is short for flux axis voltage.
Parameter number
File:group
none
Parameter type
destination
Display
x.x volts
Factory default
calculated
Minimum value
0.0 volts
Maximum value
468.8 volts
Conversion
16 = 1.0
171
Vq Max
Use Vq Max to view the Q axis voltage at which the motor enters
field weakening. The auto-tune routine calculates the value of Vq
Max. You should not change this value.
Vq is short for torque axis voltage.
Parameter number
File:group
none
Parameter type
destination
Display
x.x volts
Factory default
calculated
Minimum value
0.0 volts
Maximum value
468.8 volts
Conversion
16 = 1.0
172
Trans Dgn Config
Use Trans Dgn Config to disable certain transistor diagnostic
tests.
The bits are defined as follows:
Parameter number
File:group
Autotune:Autotune Setup
Parameter type
linkable destination
Display
bits
Factory default
00000000.00000000
Minimum value
00000000.00000000
Maximum value
00001111.11011111
Conversion
1 = 1
Refer to Chapter 13, Understanding the Auto-tuning Procedure,
for more information.
Bit
Disables:
0
Cur Fdbk U
I feedback phase U offset
1
Cur Fdbk W
I feedback phase W offset
2
Short Trans
Shorted transistor tests
3
Ground Fault
Ground fault tests
4
Open Tests
Open device tests
Bit
Disables:
5
Reserved
Leave 0.
6
Trans U Up
Power trans U upper for all tests
7
Trans U Lo
Power trans U lower for all tests
8
Trans V Up
Power trans V upper for all tests
Bit
Disables:
9
Trans V Lo
Power trans V lower for all tests
10
Trans W Up
Power trans W upper for all tests
11
Trans W Lo
Power trans W lower for all tests
12 – 15 Reserved
Leave 0.
173
Autotune/Dgn Sel
Use Autotune/Dgn Sel to select the drive diagnostic and
commissioning test.
The bits are defined as follows:
Parameter number
File:group
Autotune:Autotune Setup
Parameter type
linkable destination
Display
bits
Factory default
00000000.00000000
Minimum value
00000000.00000000
Maximum value
00000000.00111111
Conversion
1 = 1
Refer to Chapter 13, Understanding the Auto-tuning Procedure,
for more information.
Bit
Selects:
0
Trans Diag
Inverter transistor
diagnostics
1
Mtr Phas Rot
Motor phase rotation
test
Bit
Selects:
2
Lo Measure
Leakage inductance
test
3
Rs Measure
Stator resistance tests
Bit
Selects:
4
Id Measure
Flux current measure
5
Inertia
Inertia tests
Bit
Selects:
6 – 15
Reserved
Leave 0.