Atts – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 31
Mounting and Wiring Your 1336 IMPACT Drive
2-13
Catalog Number
Base Derate Amps
1
Derate Curve
2,3
Heat Dissipation Drive
Watts
Heatsink Watts
Total Watts
B075
120.3
361
1708
2069
B100
149.2
426
1944
2370
B125
180.4
522
2664
3186
BX150
180.4
606
2769
3375
B150
240.0
606
2769
3375
B200
291.4
755
3700
4455
B250
327.4
902
4100
5002
406.4
none
1005
4805
5810
BP300
406.4
4
459.2
none
1055
5455
6510
BP350
459.2
505.1
none
1295
6175
7470
BP400
481.0
570.2
none
1335
6875
8210
BP450
531.7
599.2
1395
7800
9200
673.4
1485
8767
10252
B700C
850.0
1700
9700
11400
B800C
983.0
1900
13900
500 – 600V drives
CWF10
2.5
25
29
54
CWF20
4.2
29
57
86
CWF30
6.0
32
87
119
CWF50
7.9
35
117
152
CWF75
9.9
none
91
217
308
CWF100
12.0
none
103
251
354
C015
18.9
none
117
360
477
C020
23.6
none
140
467
607
C025
30.0
none
141
492
633
C030
34.6
none
141
526
667
C040
45.1
none
175
678
853
C050
57.2
none
193
899
1092
C060
61.6
193
981
1174
C075
85.8
361
1553
1894
C100
109.1
426
1978
2504
C125
138.6
522
2162
2683
C150
159.7
C200
252.6
755
3065
3820
C250
283.6
890
3625
4515
C300
5
298.0
none
926
5015
5941
CX300
300.0
none
926
3990
4930
C350
353.6
none
1000
5935
6935
CP350
350.0
580
6125
6705
CPR 350
350.0
none
580
6125
6705
C400
406.4
1430
7120
8550
CP400
400.0
711
7000
7711
C450
459.2
1465
8020
9485
C500
505.1
1500
8925
10425
C600
599.2
1610
10767
12377
C650
673.4
1700
12000
14000
C700C
770.0
1800
9400
6
11200
C800C
800.0
2000
13300
1 Base derate amps are based on nominal voltage (240, 480, or 600V). If the input voltage exceeds the drive rating, the drive output must be
derated. Refer to Figure D.41.
2 Drive ambient temperature rating is 40 degrees C. If ambient exceeds 40 degrees C, derate the drive. Refer to Figures D.1 – D.39.
3 Drive rating is based on altitudes of 1000 m (3000 ft) or less. If installed at a higher altitude, derate the drive. Refer to Figure D.40
4 Not available at time of publication
5 IMPORTANT: Two 725 CFM fans are required if an open type drive is mounted in a user supplied enclosure.
6 This is the inverter loss only, common bus configuration 1 kHz PWM.