Specifications
Electrical
Input voltage rating*
* See the derating curves for voltages above
nominal.
200 – 240V AC, standalone, 3 phase, +10%, -15% nominal
380 – 480V AC, standalone, 3 phase, +10%, -15% nominal
500 – 600V AC, standalone, 3 phase, +10%, -15% nominal
513 – 621V DC, common bus, +10%, -15% nominal
776V DC, common bus, +10%, -15% nominal
Input power rating
2 – 134 KVA (230V)
2 – 437 KVA (380V)
2 – 555 KVA (460V)
2/3 – 578/695 KVA (500/600V)
Input frequency
50/60 Hz (
±3 Hz)
Standard output voltage
Three voltage ranges are available. Each voltage range is line dependent and can power a
motor between the following voltages:
200 – 240V AC (line dependent)
380 – 480V AC (line dependent)
500 – 600V AC (line dependent)
If the voltage required for your application is not shown, contact Allen-Bradley for specific
information.
Note: Due to internal voltage drops in the power structure and voltage margins required for
regulation, the drive is unable to produce full output voltage at base speed. If full horsepower
is required at or above base speed, an increase in current is required to produce rated
horsepower. This effect will occur in all drives, but is usually only significant in F, G, and,
especially, H frame drives since the voltage drop is proportional to source inductance and
load current.
Output power
2 – 116 KVA (230V)
2 – 190 KVA (380V)
2 – 208 KVA (415V)
2 – 537 KVA (460V)
2 – 671 KVA (575V)
Note: For information on factors that could effect the power output of the drive, please refer
to the enclosure and derating guidelines.
Output current
2.5 – 983A
Output horsepower (continuous)
7.5 – 800 hp
Overload capability
Continuous — 100% fundamental current
1 minute — 150%
Output frequency range
0 – 250 Hz
Output waveform
Sinusoidal (PWM)
Maximum short circuit current rating
200,000A rms symmetrical, 600 volts (when used with specified AC input line fuses as
detailed in Chapters 3 and 4)
Per Max Short Circuit Amps specific to each drive rating when using specified HMCP
Breakers
200,000A when using specified HMCP Breakers with Current Limit Option
Ride through
2 seconds
Efficiency
97% typical