112

mA Out Offset

Use mA Out Offset to set the offset applied to the raw milli amp
output. The offset is applied after the scale factor.

Parameter number

112

File:group

Interface/Comm:Analog Outputs

Parameter type

linkable destination

Display

±x.xxx mA

Factory default

+0.000 mA

Minimum value

-32.000 mA

Maximum value

+32.000 mA

Conversion

128 = 1.000

113

mA Out Scale

Use mA Out Scale to set the scale factor or gain for milli amp
output. A +32767 digital value is converted by the scale factor.
This allows an effective digital range of +2048 which is then
offset to provide a +20 mA range.

Parameter number

113

File:group

Interface/Comm:Analog Outputs

Parameter type

linkable destination

Display

±x.xxx

Factory default

+0.500

Minimum value

-1.000

Maximum value

+1.000

Conversion

32767 = 1.000

114

Relay Config 1

Use Relay Config 1 to select the function of terminal 1 on either
TB10 (for frames A1 – A4) or TB11 (for frames B – H) output.

Relay Config 1 may be any one of the following values:

Parameter number

114

File:group

Interface/Comm:Digital Config

Parameter type

destination

Display

x

Factory default

13

Minimum value

0

Maximum value

36

Conversion

1 = 1

Value Description

Value Description

Value Description

0

Disabled
The relay is disabled.

16

Not Zero Spd
The motor is not at zero speed.

29

Faulted

1

A fault has occurred.

1

Run Ready
The drive is ready to run.

17

Flux Ready
The motor is ready to be fluxed up.

30

Not Faulted

1

A fault has not occurred.

2

Not Run Rdy
The drive is not ready to run.

18

Not Flux Rdy
The motor is not ready to be fluxed up.

31

Warning

1

A warning has occurred.

3

Running
Commanded speed is not zero.

19

Flux Up
The drive feels the motor is fluxed up.

32

Not Warning

1

A warning has not occurred.

4

Not Running
Commanded speed is zero.

20

Not Flux Up
The drive feels the motor is not fluxed up.

33

Enable

1

Power is being applied to the
motor.

5

Stopping
The drive is stopping.

21

Jogging
The motor is jogging.

34

Not Enable

1

Power is not being applied to the
motor.

6

Not Stopping
The drive is not stopping.

22

Not Jogging
The motor is not jogging.

7

Stopped
The drive is stopped.

23

At Limit
The motor is at the limit shown in Torque
Limit Sts
(parameter 87).

35

Function Val

1

True when the value of Function
Output 1
(par. 213) and/or the
value of Function Output 2
(par. 214) are zero.

8

Not Stopped
The drive is not stopped.

24

Not At Lim
The motor is not at the limit shown in
Torque Limit Sts (parameter 87).

9

Accelerating
The motor is accelerating.

36

Not Function Val

1

True when the values of both
Function Output 1 (par. 213) and
Function Output 2 (par. 214) are
zero.

10

Not Accel
The motor is not accelerating.

25

>= Speed
The motor speed is greater than or equal to
Relay Setpoint 1 (parameter 115).

11

Decelerating
The motor is decelerating.

26

< Speed
The motor speed is less than Relay
Setpoint 1
(parameter 115).

12

Not Decel
The motor is not decelerating.

37

Function T/F
True when timer or logical state of
add/sub or mult/div is true based
on the selected function block.

13

At Set Speed
The motor is at the requested
speed.

27

>=Current
The motor current is greater than or equal
to Relay Setpoint 1 (parameter 115).

38

Not Function T/F
False when timer or logical state of
add/sub or mult/div is false based
on the selected function block.

14

Not Set Sp
The motor is not at the requested
speed.

28

The motor current is less than Relay
Setpoint 1
(parameter 115).

15

At Zero Spd
The motor is at zero speed.

1 Added for Version 2.xx.