Parameters
11-37
115
Relay Setpoint 1
Relay Setpoint 1 lets you specify the setpoint threshold for either
speed or current. Relay Setpoint 1 is only active if Relay Config 1
(parameter 114) is set to a value of 25, 26, 27, or 28.
Parameter number
File:group
Interface/Comm:Digital Config
Parameter type
linkable destination
Display
±x.x%
Factory default
+0.0%
Minimum value
-800.0%
Maximum value
+800.0%
Conversion
4096 = 100.0%
116
L Option Mode
Use L Option Mode to select the functions of L Option inputs at
TB3. If you change the value of L Option Mode, you must cycle
power before the change will take effect.
The following is the mode information:
Parameter number
File:group
Interface/Comm:Digital Config
Parameter type
destination
Display
x
Factory default
1
Minimum value
1
Maximum value
32
Conversion
1 = 1
Refer to Chapter 5, Using the L Option, for additional information.
Mode
TB3-19
TB3-20
TB3-22
TB3-23
1
Status
Stop
Status
Status
2
Start
Stop
Rev/Fwd
Jog
3
Start
Stop
Rev/Fwd
2/1Stop Type
4
Start
Stop
Rev/Fwd
2/1 Accel
5
Start
Stop
Rev/Fwd
Pot Up
6
Start
Stop
Rev/Fwd
Jog
7
Start
Stop
Rev
Fwd
8
Start
Stop
Rev
Fwd
9
Start
Stop
Pot Up
Pot Dn
10
Start
Stop
Rev
Fwd
11
Start
Stop
1st Accel
2nd Accel
12
Run Fwd
Stop
Run Rev
Loc/Rem
13
Run Fwd
Stop
Run Rev
2/1 Stop Type
14
Run Fwd
Stop
Run Rev
2/1 Accel
15
Run Fwd
Stop
Run Rev
Pot Up
16
Run Fwd
Stop
Run Rev
Loc/Rem
17
Start
Stop
Rev/Fwd
Proc Trim
18
Start
Stop
Rev/Fwd
Flux En
19
Start
Stop
Spd/Trq 3
Spd/Trq 2
20
Start
Stop
Spd/Trq 3
Spd/Trq 2
21
Start
Stop
Rev
Fwd
22
Start
Stop
Spd/Trq 3
Spd/Trq 2
23
Run Fwd
Stop
Run Rev
Proc Trim
24
Run Fwd
Stop
Run Rev
Flux En
25
Run Fwd
Stop
Run Rev
Proc Trim
Run Fwd
Stop
Run Rev
Jog
Start
Stop
Rev/Fwd
Pot Up
Start
Stop
Pot Up
Pot Dn
Start
Stop
Rev
Fwd
Run Fwd
Stop
Run Rev
Pot Up
31
3
Step Trigger Not Stop Step Trigger
Step Trigger
32
3
Start
Not Stop Step Trigger
Step Trigger
1 Added for Version 2.01.
2 Added for Version 2.02
3 Added for Version 4.01
TB3-24
TB3-26
TB3-27
TB3-28
Status
Status
Status
Status
Ext Fault
Spd 3
Spd 2
Spd 1
Ext Fault
Spd 3
Spd 2
Spd 1
Ext Fault
2/1 Decel
Spd 2
Spd 1
Ext Fault
Pot Dn
Spd 2
Spd 1
Ext Fault
Loc/Rem
Spd 2
Spd 1
Ext Fault
Jog
Spd 2
Spd 1
Ext Fault
Spd 3
Spd 2
Spd 1
Ext Fault
Spd 3
Spd 2
Spd 1
Ext Fault
Pot Up
Pot Dn
Spd 1
Ext Fault
1st Decel
2nd Decel
Spd 1
Ext Fault
Spd 3
Spd 2
Spd 1
Ext Fault
Spd 3
Spd 2
Spd 1
Ext Fault
2/1 Decel
Spd 2
Spd 1
Ext Fault
Pot Dn
Spd 2
Spd 1
Ext Fault
2/1 Stop Type Spd 2
Spd 1
Ext Fault
Ramp
Spd 2
Spd 1
Ext Fault
Reset
Spd 2
Spd 1
Ext Fault
Spd/Trq 1
Proc Trim
Spd 1
Ext Fault
Spd/Trq 1
Flux En
Spd 1
Ext Fault
Ramp
Reset
Spd 1
Ext Fault
Spd/Trq 1
Spd 2
Spd 1
Ext Fault
Reset
Spd 2
Spd 1
Ext Fault
Reset
Spd 2
Spd 1
Ext Fault
Ramp
Spd 2
Spd 1
Ext Fault
Spd 3
Spd 2
Spd 1
Ext Fault
Pot Dn
Spd 2
Spd 1
Ext Fault
Spd 3
Spd 2
Spd 1
Ext Fault
Pot Up
Pot Dn
Spd 1
Ext Fault
Pot Dn
Spd 2
Spd 1
Not Ext Flt
Step Trigger
Step Trigger
Step Trigger
Not Ext Flt
Profile Enable Run SequenceStep Hold