106 an out 1 offset, 107 an out 1 scale, 108 an out 2 value – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 233: 109 an out 2 offset, 110 an out 2 scale, 111 ma out value

Parameters
11-35
106
An Out 1 Offset
Use An Out 1 Offset to set the offset applied to the raw analog
output 1. The offset is applied after the scale factor.
Parameter number
File:group
Interface/Comm:Analog Outputs
Parameter type
linkable destination
Display
±x.xxx volts
Factory default
+0.000 volts
Minimum value
-20.000 volts
Maximum value
+20.000 volts
Conversion
205 = 1.000
107
An Out 1 Scale
Use An Out 1 Scale to set the scale factor or gain for analog
output 1. A +32767 digital value is converted by the scale factor.
This allows an effective digital range of +2048 which is then
offset to provide a +10 volt range.
Parameter number
File:group
Interface/Comm:Analog Outputs
Parameter type
linkable destination
Display
±x.xxx
Factory default
+0.500
Minimum value
-1.000
Maximum value
+1.000
Conversion
32767 = 1.000
108
An Out 2 Value
Use An Out 2 Value to convert a +32767 digital value to a +10
volt output. This is the value of the analog output number 2.
Parameter number
File:group
Interface/Comm:Analog Outputs
Parameter type
linkable destination
Display
±x
Factory default
+0
Minimum value
-32767
Maximum value
+32767
Conversion
1 = 1
109
An Out 2 Offset
Use An Out 2 Offset to set the offset applied to the raw analog
output 2. The offset is applied after the scale factor.
Parameter number
File:group
Interface/Comm:Analog Outputs
Parameter type
linkable destination
Display
±x.xxx volts
Factory default
+0.000 volts
Minimum value
-19.980 volts
Maximum value
+19.980 volts
Conversion
205 = 1.000
110
An Out 2 Scale
Use An Out 2 Scale to set the scale factor or gain for analog
output 2. A +32767 digital value is converted by the scale factor.
This allows an effective digital range of +2048 which is then
offset to provide a +10 volt range.
Parameter number
File:group
Interface/Comm:Analog Outputs
Parameter type
linkable destination
Display
±x.xxx
Factory default
+0.500
Minimum value
-1.000
Maximum value
+1.000
Conversion
32767 = 1.000
111
mA Out Value
Use mA Out Value to convert a +32767 digital value to a
4 – 20 mA output. This is the value of the mA output.
Parameter number
File:group
Interface/Comm:Analog Outputs
Parameter type
linkable destination
Display
±x
Factory default
+0
Minimum value
-32767
Maximum value
+32767
Conversion
1 = 1