55 ptrim kp, 56 reserved, 57 reserved – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 221: 58 ptrim lo limit, 59 ptrim hi limit

Parameters
11-23
55
PTrim Kp
Use PTrim Kp to control the proportional gain of the process trim
regulator. If the Kp process trim is equal to 1.0, the process trim
PI regulator output equals 1 pu for 1 pu process trim error.
Parameter number
File:group
Application:Process Trim
Parameter type
linkable destination
Display
x.xxx
Factory default
1.000
Minimum value
0.000
Maximum value
16.000
Conversion
4096 = 1.000
Refer to the Trim Control Overview section in Appendix B,
Control Block Diagrams, for more information.
56
Reserved
Leave this parameter set to 0.
Parameter number
File:group
Parameter type
Display
Factory default
Minimum value
Maximum value
Conversion
57
Reserved
Leave this parameter set to 0.
Parameter number
File:group
Parameter type
Display
Factory default
Minimum value
Maximum value
Conversion
58
PTrim Lo Limit
Use PTrim Lo Limit to specify the low limit of the process trim
regulator output value. The output of the process trim regulator is
limited by adjustable high and low limits.
Parameter number
File:group
Application:Process Trim
Parameter type
linkable destination
Display
±x.x%
Factory default
-100.0%
Minimum value
-800.0%
Maximum value
+800.0%
Conversion
4096 = 100.0%
Refer to the Trim Control Overview section in Appendix B,
Control Block Diagrams, for more information.
59
PTrim Hi Limit
Use PTrim Hi Limit to specify the high limit of the process trim
regulator output value. The output of the process trim regulator is
limited by adjustable high and low limits.
Parameter number
File:group
Application:Process Trim
Parameter type
linkable destination
Display
±x.x%
Factory default
+100.0%
Minimum value
-800.0%
Maximum value
+800.0%
Conversion
4096 = 100.0%
Refer to the Trim Control Overview section in Appendix B,
Control Block Diagrams, for more information.