beautypg.com

Hard wiring your i/o, Hard wiring your i/o -8 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 66

background image

4-8

Mounting and Wiring Information Specific to Frames B, C, D, E, F, G, and H

Hard Wiring Your I/O

You can use terminal blocks TB10 and TB11 for hard wiring your
I/O. These terminals are shown in Figure 4.6.

Figure 4.6
Reference Signal Connections

1

2

3

4

5

6

7

8

9

10

Relay 1

Default: At Speed

Supply

Relay 2

Default: Enable

(Run)

Relay 3

Default: Not Fault

Relay 4

Default: Not Warning

(Alarm)

TE

TB11

13 14 15 16 17 18 19 20 21 22

Analog
Input 1

TB10

1

2

3

4

5

6

7

8

9 10 11 12

DC Power

Supply

+10V Com -10V

+

+

+

+

+

+

+

-

-

-

-

-

-

-

SH

SH

SH

SH

SH

Analog
Input 2

4-20 mA
Input

Pulse
Source

Analog
Output 1*

Analog
Output 2*

4-20 mA
Output*

Voltage
Clearance

SH = Shield

NOTE: Analog I/O is differential, non-isolated I/O. A negative (-) does not
Indicate common.