252 step 2 speed, 253 step 2 value, 254 step 2 type – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 275: 255 step 3 speed, 256 step 3 value, 257 step 3 type

Parameters
11-77
252
Step 2 Speed
Parameter 252 sets the rpm value for this step. (Scaling: 4096 =
Base Speed)
Parameter number
252
File:group
Profile Test Data
Parameter type
Setup
Display
+/- x.x rpm
Factory default
+0.0 rpm
Minimum value
-8 x base speed
Maximum value
+8 x base speed
Conversion
4096 = Base Motor Speed
253
Step 2 Value
Parameter 253 sets the time in seconds for time steps, the
counts in units for encoder steps, and the TB3 input to trigger on
for TB Input steps. Scaling:
Time Step: 10 x desired value (10 = 1.0 sec)
Encoder Step: 10 = 1.0 unit
TB Input Step: dependent on [L Option Mode Sel]. See P241.
Parameter number
253
File:group
Profile Test Data
Parameter type
Setup
Display
x.xS, x, x.x units
Factory default
0.0,0, 0.0
Minimum value
0.0,0, 0.0
Maximum value
3276.7, 5, 3276.7
Conversion
0=1.0 sec., x TBin, 10 = 1.0 unit
254
Step 2 Type
Parameter 251 selects the type of step to be used
0 = Not Used (This forces an End Action)
1 = Time Step, operate at speed shown in P252 for time in P253.
2 = TB3 Input Step, operate at speed shown in P252 until this
input goes true.
3 = Encoder Step, operate at speed shown in P252 for units in
P253.
Parameter number
254
File:group
Profile Test Data
Parameter type
Setup
Display
x
Factory default
0
Minimum value
0
Maximum value
3
Conversion
None
255
Step 3 Speed
Parameter 255 sets the rpm value for this step. (Scaling: 4096 =
Base Speed)
Parameter number
255
File:group
Profile Test Data
Parameter type
Setup
Display
+/- x.x rpm
Factory default
+0.0 rpm
Minimum value
-8 x base speed
Maximum value
+8 x base speed
Conversion
4096 = Base Motor Speed
256
Step 3 Value
Parameter 256 sets the time in seconds for time steps, the
counts in units for encoder steps, and the TB3 input to trigger on
for TB Input steps. Scaling:
Time Step: 10 x desired value (10 = 1.0 sec)
Encoder Step: 10 = 1.0 units
TB Input Step: dependent on [L Option Mode Sel]. See P241.
Parameter number
256
File:group
Profile Test Data
Parameter type
Setup
Display
x.xS, x, x.x units
Factory default
0.0,0, 0.0
Minimum value
0.0,0, 0.0
Maximum value
3276.7, 5, 3276.7
Conversion
0=1.0 sec., x TBin, 10 = 1 unit
257
Step 3 Type
Parameter 257 selects the type of step to be used
0 = Not Used (This forces an End Action)
1 = Time Step, operate at speed shown in P255 for time in P256.
2 = TB3 Input Step, operate at speed shown in P255 until this
input goes true.
3 = Encoder Step, operate at speed shown in P255 for units in
P256.
Parameter number
257
File:group
Profile Test Data
Parameter type
Setup
Display
x
Factory default
0
Minimum value
0
Maximum value
3
Conversion
None