Control Block Diagrams

B-9

To by-pass the acceleration and deceleration ramps, use a
communications module or an L Option board to set bit 9 of Logic
Input Sts
(parameter 14). You can also by-pass the ramps by setting
the appropriate Accel/Decel Time parameters (parameters 42, 43, 44,
and 45) to zero.

50%

The S-curve is applied to 50% of the ramp time.

100%

The S-curve is applied to 100% of the ramp time.

If S-Curve Percent is

set to:

Then:

Speed

Time (in seconds)

0

0

Ramp Out

Speed

Time (in seconds)

0

0

Ramp Out