Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 385
Using the Human Interface Module (HIM)
C-9
Using the Control Status Mode
Control Status mode lets you enable/disable the drive logic and check
the fault and warning queues.
Using Control Logic
The Control Logic option lets you disable the drive logic mask to
prevent a serial fault when the HIM is removed with the drive power
applied.
To use Control Logic:
1. From the status display, press any key. Choose Mode is shown.
2. Press INC or DEC to show Control Status.
3. Press ENTER.
4. Press INC or DEC until Control Logic is displayed.
5. Press ENTER.
6. Press SEL.
7. Press INC or DEC to select either Disabled (or Enabled).
8. Press ENTER. The logic mask is now disabled (or enabled).
Viewing the Fault Queue/Warning Queue
To view either the fault or the warning queue:
1. Press any key from the status display. Choose Mode is shown.
2. Press INC or DEC to show Control Status.
3. Press ENTER.
4. Press INC or DEC until Fault Queue or Warning Queue is
displayed.
5. Press ENTER.
6. Press INC or DEC until View Queue is displayed.
7. Press ENTER.
The fault queue can contain up to 32 faults. The 1336 IMPACT drive
reports the faults using the following format:
The trip indicator is only present if this fault caused the drive to trip.
The last number (1) indicates this fault’s position within the fault
queue.
Control Status mode is only available with a Series A (version 3.0)
or Series B HIM.
I n v
O v e r T e m p
T r p
F
2 0 2 8
T r
i p
1
Fault name
Fault queue
indicator
Fault code
number
Trip indicator
Position in