96 an in 1 value, 97 an in 1 offset, 98 an in 1 scale – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 231: 99 an in 2 value

Parameters
11-33
If you enter this value for Test
Select 2 (parameter 95):
Then, the value in Test Data 2 (parameter 94) represents the:
hours
minutes/seconds
11124
11224
The time since power up that the fault in position 24 occurred
11125
11225
The time since power up that the fault in position 25 occurred
11126
11226
The time since power up that the fault in position 26 occurred
11127
11227
The time since power up that the fault in position 27 occurred
11128
11228
The time since power up that the fault in position 28 occurred
11129
11229
The time since power up that the fault in position 29 occurred
11130
11230
The time since power up that the fault in position 30 occurred
11131
11231
The time since power up that the fault in position 31 occurred
11132
11232
The time since power up that the fault in position 32 occurred
58144
Drive software version (example: 101)
58146
Drive power structure type
58220
Speed regulator output
58228
Speed error (reference — feedback)
58230
Unfiltered speed feedback (4096 @ Nameplate RPM)
58250
Internal torque reference (4096 @ rated motor torque)
58296
Inverter temperature feedback (degrees Celsius)
96
An In 1 Value
Use An In 1 Value to view the converted analog value of the input
at analog input 1.
Parameter number
File:group
Interface/Comm:Analog Inputs
Parameter type
source
Display
±x
Factory default
not applicable
Minimum value
-32767
Maximum value
+32767
Conversion
1 = 1
97
An In 1 Offset
Use An In 1 Offset to set the offset applied to the raw analog
value of the analog input 1 before the scale factor is applied. This
lets you shift the range of the analog input.
Parameter number
File:group
Interface/Comm:Analog Inputs
Parameter type
linkable destination
Display
±x.xxx volts
Factory default
0.000 volts
Minimum value
-19.980 volts
Maximum value
+19.980 volts
Conversion
205 = 1.000
98
An In 1 Scale
Use An In 1 Scale to set the scale factor or gain for analog
input 1. The value of analog input 1 is converted to +2048 and
then the scale is applied. This provides an effective digital range
of
±32767.
Parameter number
File:group
Interface/Comm:Analog Inputs
Parameter type
linkable destination
Display
±x.xxx
Factory default
+2.000
Minimum value
-16.000
Maximum value
+16.000
Conversion
2048 = 1.000
99
An In 2 Value
Use An In 2 Value to view the converted analog value of the input
at analog input 2.
Parameter number
File:group
Interface/Comm:Analog Inputs
Parameter type
source
Display
±x
Factory default
not applicable
Minimum value
-32767
Maximum value
+32767
Conversion
1 = 1