Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 25
![background image](/manuals/578736/25/background.png)
Mounting and Wiring Your 1336 IMPACT Drive
2-7
NA = Not Available, use fuses
1
Bulletin 140 - At 480 volts, circuit breaker must have a fuse backup. Refer to the
AB Industrial Control Catalog. At 600 volts, additional restrictions apply. No
limitations in source short circuit ratings.
2
HMCP Circuit Breaker - HMCP Breaker is a magnetic trip device only. Always set
the trip setting as low as possible in a particular application.
3
Current limiting option can extend this value to 200,000A RMS
1336E-B350
298 (400)
NA
NA
NA
-
-
1336E-BP350
261 (350)
NA
NA
HMCP600L6W
E
65,000
1336E-B400
336 (450)
NA
NA
NA
-
-
1336E-BP400
298 (400)
NA
NA
HMCP600L6W
E
65,000
1336E-B450
373 (500)
NA
NA
NA
-
-
1336E-BP450
336 (450)
NA
NA
HMCP600L6W
E
65,000
1336E-B500
448 (600)
NA
NA
NA
-
-
1336E-C001
0.75 (1)
140-MN-0400
100,000
HMCPS003A0
E
65,000
1336E-C003
2.2 (3)
140-MN-0630
100,000
HMCPS007C0
E
65,000
1336E-C007
5.5 (7.5)
140-MN-1000
16,000
HMCPS015E0C
E
65,000
1336E-C010
7.5 (10)
140-MN-1600
6,000
HMCPS015E0C
E
65,000
1336E-C015
11 (15)
140-MN-2000
6,000
HMCPS030H1C
F
65,000
1336E-C020
15 (20)
140-MN-2500
6,000
HMCPS030H1C
H
65,000
1336E-C025
18.5 (25)
140-CMN-4000
65,000
HMCPS050K2C
E
65,000
1336E-C030
22 (30)
140-CMN-4000
65,000
HMCPS050K2C
G
65,000
1336E-C040
30 (40)
140-CMN-6300
50,000
HMCPS050K2C
G
65,000
1336E-C050
37 (50)
140-CMN-6300
50,000
HMCPS100R3C
E
65,000
1336E-C060
45 (60)
140-CMN-6300
50,000
HMCPS100R3C
E
65,000
1336E-C075
56 (75)
140-CMN-9000
25,000
HMCPS100R3C
G
65,000
1336E-C100
75 (100)
KTA3-160S-125
65,000
HMCP150T4C
E
65,000
1336E-C125
93 (125)
KTA3-160S-160
65,000
HMCP150T4C
E
65,000
1336E-C150
112 (150)
KTA3-400S-160
65,000
HMCP150T4C
G
65,000
1336E-C200
149 (200)
KTA-400S-320
65,000
HMCP250J5
I
65,000
1336E-C250
187 (250)
KTA3-400S-320
65,000
HMCP400W5
G
65,000
1336E-CX300
224 (300)
KTA3-400S-320
65,000
HMCP400W5
H
65,000
1336E-C300
224 (300)
KTA3-400S-320
65,000
HMCP400W5
H
65,000
1336E-C350
261 (350)
KTA3-400S-320
65,000
NA
NA
NA
1336E-C400
298 (400)
KTA3-400S-320
65,000
NA
NA
NA
1336E-C450
336 (450)
NA
NA
NA
NA
NA
1336E-C500
373 (500)
NA
NA
NA
NA
NA
1336E-C600
448 (600)
NA
NA
NA
NA
NA
Drive
Catalog Number
Maximum
Rated Vt
kW (HP)
IEC Installations per IEC947-2
UL/CSA Installations
Bulletin 140 Circuit Breaker
HMCP Circuit Breaker
2
Catalog Number
Rated Service Short
Circuit Capability
400/415V
Catalog Number
MCP Trip
Setting
Max. Short
Circuit Amps
3
480V