125 dir/ref mask, 126 start/jog mask – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 238
11-40
Parameters
125
Dir/Ref Mask
You can use the lower byte of Dir/Ref Mask (bits 0 through 7) to
select which SCANport device can issue a reference command.
You can use the higher byte (bits 8 through 15) to select which
SCANport devices can issue a forward/reverse direction
command. You can choose between:
0 = Disable control
1 = Enable control
The bits are defined as follows:
Parameter number
File:group
Interface/Comm:SCANport Config
Parameter type
linkable destination
Display
bits
Factory default
11111111.11111111
Minimum value
00000000.00000000
Maximum value
11111111.11111111
Conversion
1 = 1
Refer to Chapter 8, Using the SCANport Capabilities, for more
information.
Bit
Description
0
Refer L Opt
Let the L Option board control the
reference.
1
Refer SP 1
Let SCANport device 1 control
the reference.
2
Refer SP 2
Let SCANport device 2 control
the reference.
3
Refer SP 3
Let SCANport device 3 control
the reference.
4
Refer SP 4
Let SCANport device 4 control
the reference.
5
Refer SP 5
Let SCANport device 5 control
the reference.
Bit
Description
6
Refer SP 6
Let SCANport device 6 control
the reference.
7
Refer P197
Let Logic Cmd Input
(parameter 197) control the
reference.
8
Direct L Opt
Let the L Option board control the
direction.
9
Direct SP 1
Let SCANport device 1 control
the direction.
10
Direct SP 2
Let SCANport device 2 control
the direction.
11
Direct SP 3
Let SCANport device 3 control
the direction.
Bit
Description
12
Direct SP 4
Let SCANport device 4 control
the direction.
13
Direct SP 5
Let SCANport device 5 control
the direction.
14
Direct SP 6
Let SCANport device 6 control
the direction.
15
Direct P197
Let Logic Cmd Input
(parameter 197) control the
direction.
126
Start/Jog Mask
You can use the lower byte of Start/Jog Mask (bits 0 through 7) to
select which SCANport devices can issue a jog reference
command. You can use the higher byte (bits 8 through 15) to
select which SCANport devices can issue a start command. You
can choose between:
0 = Disable control
1 = Enable control
The bits are defined as follows:
Parameter number
File:group
Interface/Comm:SCANport Config
Parameter type
linkable destination
Display
bits
Factory default
11111111.11111111
Minimum value
00000000.00000000
Maximum value
11111111.11111111
Conversion
1 = 1
Refer to Chapter 8, Using the SCANport Capabilities, for more
information.
Bit
Description
0
Jog L Opt
Let the L Option board control
jogs.
1
Jog SP 1
Let SCANport device 1 control
jogs.
2
Jog SP 2
Let SCANport device 2 control
jogs.
3
Jog SP 3
Let SCANport device 3 control
jogs.
4
Jog SP 4
Let SCANport device 4 control
jogs.
5
Jog SP 5
Let SCANport device 5 control
jogs.
Bit
Description
6
Jog SP 6
Let SCANport device 6 control
jogs.
7
Jog P197
Let Logic Cmd Input
(parameter 197) control jogs.
8
Start L Opt
Let the L Option board control
starts.
9
Start SP 1
Let SCANport device 1 control
starts.
10
Start SP 2
Let SCANport device 2 control
starts.
11
Start SP 3
Let SCANport device 3 control
starts.
Bit
Description
12
Start SP 4
Let SCANport device 4 control
starts.
13
Start SP 5
Let SCANport device 5 control
starts.
14
Start SP 6
Let SCANport device 6 control
starts.
15
Start P197
Let Logic Cmd Input
(parameter 197) control starts.