Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 22

2-4
Mounting and Wiring Your 1336 IMPACT Drive
Table 2.B
Maximum Motor Cable Length Restrictions — 500V – 600V Drives
3
All Cable Lengths Given in meters (feet)
.
NR = Not Recommended
Drive
Frame
Drive kW (hp)
Motor kW
(hp)
No External Devices
w/1204-TFB2 Terminator
w/1204-TFA1 Terminator
Reactor at Drive
1
Motor w/Insulation V
P-P
Motor w/Insulation V
P-P
Motor w/Insulation V
P-P
Motor w/Insulation V
P-P
1000V
1200V
1600V
2
1000V
1200V
1600V
1000V
1200V
1600V
1000V
1200V
1600V
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
A4
0.75 (1)
0.75 (1)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
Not
Recommended
0.37 (0.5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.5 (2)
1.5 (2)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.2 (1.5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.75 (1)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.37 (0.5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
2.2 (3)
2.2 (3)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.5 (2)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.75 (1)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.37 (0.5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
3.7 (5)
3.7 (5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
2.2 (3)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.5 (2)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.75 (1)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.37 (0.5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
B
5.5 – 15
(7.5 – 20)
5.5 – 15
(7.5 – 20)
NR
9.1
(30)
15.2
(50)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
30.5
(100)
91.4
(300)
182.9
(600)
C
18.5 – 45
(25 – 60)
18.5 – 45
(25 – 60)
NR
9.1
(30)
12.2
(40)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
30.5
(100)
91.4
(300)
182.9
(600)
D
56 – 93
(75 – 125)
56 – 93
(75 – 125)
NR
9.1
(30)
33.5
(110)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
61.0
(200)
91.4
(300)
182.9
(600)
E
112 – 224
(150 – X300)
112 – 224
(150 – X300)
NR
9.1
(30)
21.3
(70)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
F
224 – 336
(300 – 450)
224 – 336
(300 – 450)
NR
9.1
(30)
41.1
(135)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
G
224 – 448
(300 – 600)
224 – 448
(300 – 600)
NR
9.1
(30)
41.1
(135)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
H
522 – 597
(700 – 800)
522 – 597
(700 – 800)
NR
9.1
(30)
41.1
(135)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
1
A 3% reactor reduces motor and cable stress but may cause a degradation of motor waveform quality. Reactors must have a turn-turn insulation rating of 2100
volts or higher.
2
1329R only
3
Values shown are for nominal input voltage and drive carrier frequency of 2 kHz. Consult factory regarding operation at carrier frequencies above 2 kHz. Multiply
values by 0.85 for high line conditions.